Manual eXP

Right choice for ultimate yield!
LSIS strives to maximize customer’s profit in gratitude of choosing us for your partner.
Human Machine Interface
XGT PANEL
eXP Series User’s Manual
eXP20-TTA
eXP40-TTA
eXP40-TTB
eXP40-TTE
eXP60-TTA
eXP60-TTB
Read this manual carefully before
installing, wiring, operating, servicing
or inspecting this equipment.
Keep this manual within easy reach
for quick reference.

 

Safety Precautions

1
Before using the product…
To use the product safety and effectively, please read this instruction manual thoroughly before use.
Please keep to the safety precaution, for it to prevent accidents and potential danger from
occurring.
Safety precaution is classified into ‘Warming’ and ‘Caution’ and their meanings are as follows.
Warning Violating the instruction may result in serious personal injury or death.
Caution Violating the instruction may result in slight personal injury or product
damage.
The indicated illustrations on the product and in the manual have the fallowing meanings.
Be cautions, for danger may be present.
Be cautions, for there is a possibility of an electric shock.
After reading the instruction manual, keep it handy for quick reference.

Safety Precautions

 

2

Design Precautions
Design Precautions
Installation Precautions
Install a safety circuit external to the HMI to protect the whole control system in case of
external power supply trouble.
Serious trouble may occur to the entire system due to erroneous output/operation of the HMI.
Warning
In/output signal or communication cable should be at least 100mm apart from Highvoltage/power wires.
Otherwise, it may cause erroneous output/operation.
Use the HMI in an environment that meets the general specification contained in this
manual or datasheet.
Otherwise, it could result in electric shock, fire, erroneous operation or deterioration.
In case of much vibration in the installed environment, be sure to insulate the HMI from
direct vibration.
Otherwise, it could result in electric shock, fire, erroneous operation.
Be sure not to let foreign substances such as conductive debris inside the product.
Otherwise, it could result in electric shock, fire, erroneous operation.
Caution
Caution

Safety Precautions

3
Wiring Precautions
Be sure to turn off the HMI and external power before wiring.
Otherwise, it may result in an electric shock or damage to the product.
Wire correctly by checking each of the product’s rated voltage and terminal layout.
Otherwise, it may result in fire, electric shock or erroneous operation.
Tighten terminal screws with specified torque when wiring.
If terminal screws are loose, it may result in short circuits, fire or erroneous operation.
Use the exclusive HMI 3-type grounding for the FG terminal.
If not grounded, it may result in erroneous operation.
Be sure not to let any foreign substances such as wiring debris inside the module.
Such debris may cause fire, damage or erroneous operation.
Warning
Caution

Safety Precautions

 

4

Startup and Maintenance Precautions
Disposal Precaution
Do not touch the terminals while power is on.
Otherwise, it may cause electric shock or erroneous operation.
Turn off the HMI and external power when cleaning or tightening the terminal.
Otherwise, it may cause electric shock or erroneous operation.
Do not charge, disassemble, heat, short circuit, solder, etc. other battery.
Mishandling the battery may cause overheating, crack, fire and may result in injury or fire.
Do not disassemble PCB from the product case or modify the product.
Otherwise, it may result in fire, electric shock or erroneous operation.
Use cellular phone or walky-talky at least 30cm away from the HMI.
Otherwise, it may result in erroneous operation.
When disposing of this product or battery, treat it as industrial waste.
Otherwise, it may cause poisonous pollution or explosion.
Warning
Caution
Caution

Revision History

5
Revision History

Version Date Contents Revised location
V1.0 ‘16.05 First Edition -
V1.1 ’16.07 Additional model (eXP20-TTA/DC) -

-
The number of User’s manual is indicated the right side of the back cover.
ⓒ LSIS Co.,Ltd 2016 All Rights Reserved.

Contents

 

C
hapter 1 General Introduction ...................................................................... 1-1~1-6

6
1.1 How to use the Instruction Manual........................................................................................................1-1
1.2 Feature ..................................................................................................................................................1-2
1.3 Terminology...........................................................................................................................................1-6

Chapter 2 System Configuration ....................................................................... 2-1~2-6

2.1 Part Names ...........................................................................................................................................2-1
2.2 System Configuration............................................................................................................................2-5

Chapter 3 Standard Specification.................................................................... 3-1~3-4

3.1 General Standards ................................................................................................................................3-1
3.2 Function Standards ...............................................................................................................................3-3

Chapter 4 System Configuration ................................................................... 4-1~4-13

4.1 Backlight Setting ...................................................................................................................................4-2
4.2 Touch Calibration ..................................................................................................................................4-3
4.3 Date Time Setting .................................................................................................................................4-4
4.4 Environment Setting..............................................................................................................................4-5
4.5 Ethernet Setting ..................................................................................................................................4-11
4.6 XP-Remote Setting .............................................................................................................................4-12
4.7 Buzzer Setting.....................................................................................................................................4-13

Chapter 5 Diagnostics ...................................................................................... 5-1~5-8

5.1 Screen Diagnosis ..................................................................................................................................5-2
5.2 Touch Diagnosis ...................................................................................................................................5-3
5.3 Backup Memory Diagnosis ...................................................................................................................5-4
5.4 Flash Memory Diagnosis.......................................................................................................................5-5
5.5 USB Memory Diagnosis ........................................................................................................................5-6
5.6 Serial Communication Diagnosis ..........................................................................................................5-7

Contents

7

Chapter 6 Viewing Information of PLC Connection Status .......................... 6-1~6-8

6.1 PLC Communication Configuration Settings.........................................................................................6-2
6.2 Connection Information .........................................................................................................................6-3
6.3 PLC Information ....................................................................................................................................6-4
6.4 History of PLC Error ............................................................................................................................6-4
6.5 History of PLC Mode Conversion ........................................................................................................6-5
6.6 History of PLC Power ..........................................................................................................................6-5
6.7 History of PLC System ........................................................................................................................6-6
6.8 N:1 Settings .........................................................................................................................................6-7
6.9 Program Monitor ..................................................................................................................................6-8

Chapter 7 Storage Function ............................................................................. 7-1~7-4

7.1 General Introduction ............................................................................................................................7-1
7.2 Downloading Project through the Storage Equipment..........................................................................7-2
7.3 Uploading Project through the Storage Equipment...............................................................................7-3
7.4 Updating the Device through Storage Equipment.................................................................................7-4

Chapter 8 XGT Panel S/W Update........................................................................... 8-1

8.1 General Introduction ............................................................................................................................8-1

Chapter 9 File Backup through External Storage Equipment....................... 9-1~9-7

9.1 Path Structure in case of File Backup...................................................................................................9-1
9.2 Operation setting when there is no space for backup...........................................................................9-5
9.3 Structure of path of video file and video capture files ...........................................................................9-6

Contents

8

Chapter 10 Installation and Wiring ............................................................ 10-1~10-10

10.1 Installation .........................................................................................................................................10-1
10.1.1 Installation environment...........................................................................................................10-1
10.1.2 Notice in handling ....................................................................................................................10-3
10.1.3 Notice in installing the panel....................................................................................................10-3
10.2 Wiring ................................................................................................................................................10-7
10.2.1 Power wiring ............................................................................................................................10-7
10.2.2 Ground wiring ........................................................................................................................10-10

Chapter 11 Maintenance............................................................................... 11-1~11-3

11.1 Maintenance......................................................................................................................................11-1
11.2 Daily Maintenance.............................................................................................................................11-1
11.3 Periodical Maintenance.....................................................................................................................11-2

Chapter. 12 EMC Standard Certification .................................................... 12-1~12-2

12.1 Requirement for EMC Standard Certification ..................................................................................12-1
12.1.1 CE standard certification ........................................................................................................12-1
12.1.2 KC standard certification ........................................................................................................12-2
12.2 Requirement for Low Voltage Command Suitability .........................................................................12-2
12.2.1 Standard certification for XGT Panel.......................................................................................12-2
12.2.2 Selection of XGT Panel .........................................................................................................12-2

Appendix 1 Troubleshooting............................................................ App1-1~App1-24

1. Type of Problem.............................................................................................................................. App 1-1
2. Problem when Starting.................................................................................................................... App 1-2
3. Problem after the Monitor on........................................................................................................... App 1-4
4. Display Problem of Figure and Object ............................................................................................ App 1-6
5. Communication Problem................................................................................................................. App 1-9
6. USB Removal of Memory Card..................................................................................................... App 1-10
7. Error Message during Execution of Program................................................................................ App 1-11

Appendix 2 Dimension .................................................................... App 2-1~ App 2-3

 

Appendix 3 Warranty and Environmental Policy........................................... App 3-1

 

Chapter 1 General Introduction

1-1
Chapter 1 General Introduction
1.1 How to use the Instruction Manual
This instruction manual provides information such as specification, how to use, etc., of the product needed to operate eXP
series of XGT Panel.
The user manual’s configuration is as follows.

Sequence Category Contents
Chapter1 General Introduction It describes this manual’s configuration, product’s feature and term.
Chapter2 System Configuration It describes feature and system configuration of each XGT Panel.
Chapter3 Standard Specification It describes XGT Panel’s general and function specification.
Chapter4 System Configuration It describes XGT Panel’s system configuration.
Chapter5 Diagnostics It describes XGT Panel’s self-diagnosis.
Chapter6 Viewing information of
PLC Connection Status
It describes the way on connection status information of PLC which is
connected with XGT Panel.
Chapter7 Transmission of Project
from USB Storage
Device
It describes the way to execute the project by using USB storage
device.
Chapter8 XGT Panel S/W Update It describes the way to update engine at XGT Panel.
Chapter9 Backup files by using
Storage Devices
It describes the way to backup recipe, logging and etc. files by using
storage devices.
Chapter10 Installation and Wiring It describes an installation, wiring and caution for reliability of PLC
system.
Chapter11 Maintenance It describes inspection category and method for long normal operation
of PLC system.
Chapter12 EMC Standard It describes system configuration for EMC standard.
Appendix 1 Troubleshooting It describes a variety of error contents and measure.
Appendix 2 Dimension It describes the dimension of XGT Panel.
Appendix 3 Warranty and
Environment Policy
-

 

Remark
This manual doesn’t describe connection with XP-Builder and PLC. For their own function, Please refer to the related
manuals.

 

Chapter 1 General Introduction
1.2 Feature

1-2
XGT Panel series has the following features.
(1) Various types of external interface
(a) Supporting various device of USB, Ethernet, it maximizes the customer’s usability.
Various communication connectors are placed at the lower side so that it can be connected in a variety
of types with the control device such as PLC, inverter, etc. Through RS-485, RS-232C, RS-422/485,
Ethernet (10Base-T /100Base-TX) communication, it can be connected with control device.
Status LED
-When power on, LED light
USB DEVICE(eXP40/60)
- Project download through
XP-Builder
Battery Cover
- Reset Switch
- Battery,
- Setting Switch,
RS-422/485(eXP40/60)
-Control device that can be communicated such as
PLC
USB HOST
-Data Backup
(alarm, logging, recipe, etc.)
-Project data storage
(image, upload project, etc.)
-Mouse, Keyboard, Printer
RS-485(eXP40/60)
RS-422/485(eXP20)
- Control device that can be
communicated such as PLC
Ethernet
- Project downloads through XPBuilder
-Control device that can be
communicated
such as PLC
-Connected with fieldbus and
Power Terminal
-Composed of power input
and PE terminal
RS-232C
- Control device that can
be communicated such as
PLC

Chapter 1 General Introduction

1-3
(2) Based on Windows CE
(a) Adoption of Microsoft Company’s Windows CE
Windows CE 6.0
(b) Advantage
It provides stable software capacity by using Microsoft Company’s platform.
It can process diverse function simultaneously.
It provides diverse interface including Ethernet, USB.
The user interface including mouse and keyboard can be connected.
It has high flexibility like computer software.
Fast reaction is available when adding new equipment.
Wide data sharing and management with upper system is available (Later).
(3) Improvement of project transmission time
(a) It provides Ethernet which is faster than RS-232C.
(b) It provides the transmission function from USB storage device.
(4) High quality screen
(a) It provides the high quality screen and clearness by high quality LCD.
It adopts TFT LCD which supports the 65,536 Color.
(b) It provides diverse graphic type.
It is available to express precisely and actually.
It provides the simple moving function with GIF support.
(5) Analog touch Panel
(a) It adopts analog (resistive) Touch Panel.
Visibility is improved without the grids.

Chapter 1 General Introduction

1-4
(b) It provides high touch resolution.
It can control Touch Panel precisely.
(6) Multilingual and diverse font
(a) It supports the multilingual function.
It transmits the Windows/User font used in computer to XGT Panel.
Additional language development is not necessary.
Multilingual language is an advantage of Windows CE.
(b) It can express twelve kinds of language simultaneously.
It can express 12 kinds of language simultaneously.
Language switching is available by using special switch during operation.
(c) It can provide the various fonts.
Various expressions are available by using the Windows/User font.
Font size and type can be adjusted freely.

Chapter 1 General Introduction

1-5
(7) Advanced function
(a) Alarm function.
The History alarm can be classified alarm group and alarm list and selected alarm can be expressed
by alarm search.
The Flow alarm indicates current or the latest alarm at the bottom of screen.
The System alarm indicates the important problems from operation.
(b) Logging function
It provides conditional logging according to device condition and continuous periodic logging which
operates periodically according to time and device status.
It provides 256Kbyte areas for backup.
Backup into USB storage device is available.
Backup data’s type is stored in Excel, it is easy to use.
(c) Recipe function.
It provides READ/WRITE function.
It provides 128Kbyte areas for backups. [General recipe: it set up 10,000 double words for each of
one of them.]
Backup into the USB storage device is available.
Backup data’s type is stored in Excel, it is easy to use.
(d) Scheduler function.
It can be set up to Max. 32.
(e) Print function.
It provides a Screen/Alarm print function.
It can be printed by USB printer.
(f) Script function.
It provides more flexible function by user Script.
It can be diversely applied to such as including Global/Object/Screen indication and so on.
(8) Stable product suitable for international standards
(a) CE, KC standard acquisition
(b) UL(cUL) standard acquisition

Chapter 1 General Introduction

1-6
1.3 Terminology
It describes terms used in this manual.

Term Definition Remarks
Module A standard element that has a specified function which configures the
system.
Devices such as I/O board, which inserted onto the mother board or
base unit..
Ex) CPU module,
Power Module,
I/O module
Unit A single module or group of modules that perform an independent
operation as a part of PLC system.
Ex) Basic unit,
Extension unit
PLC system System consisted of PLC and peripheral device which can be
controlled by user program.
-
XP-Builder Software used to write and edit the project. -
XP-Manager It is the software for edition, download, monitoring to realize data
communication between XGT Panels through XP Link with online
control function.
XP-Remote Software used to remote monitor and control the XGT Panel
Cnet module Computer Link -
FEnet module Fast Ethernet Network -
RTC Abbreviation of ‘Real Time Clock’.
It is used to call general IC that contains clock function.
-

 

Chapter 2 System Configuration

2-1
Chapter 2 System Configuration
Characteristic of each eXP series and its system configuration are as follow;
2.1 Part Names
1. eXP20-TTA

Items Part Names Descriptions
Front Part 1) Analog Touch Panel: Input by user’s touch
2) LCD: Screen indication
Power LED Indicating the state of device (On: BLUE)
High Luminance Blue LED
Panel Mounting
Panel
Fixing XGT Panel on the panel using bracket

 

Chapter 2 System Configuration

2-2

Items Part Names Descriptions
Power Terminal Composed of Power Input(DC24V) and PE Terminal
USB Interface 1) USB Memory Connection: Backup of data such as alarm/logging/recipe
and
storage of screen data
2) USB Memory Connection: Send/Receive project data, Send XP-Runtime
3) User’s Interface Connection: Using mouse/keyboard
4) Printer connection: Printing function
Battery Cover
Reset Switch
Backup Battery
Setting Switch
<Setting Switch>

No.1 A Config. Backup Battery On
B Config. Backup Battery Off
No.2 /
3
A Config. RS-422/485 Terminating Resistance On
B Config. RS-422/485 Terminating Resistance Off
No. 4 A Config. O/S Download Mode
B Config. Operating Mode
Ethernet Terminal Ethernet: 10Base-T/ 100Base-TX
1) Send Project Data
2) Receive backup data and project file
3) Send XP-Runtime
4) PLC/Control Device Communication
RS-232C, RS-
422/485 Connector
RS-232C (COM2): PLC/ Control Device Communication
RS-422/485 (COM3): PLC/ Control Device Communication
COM1 is not used.

 

Chapter 2 System Configuration

2-3
1. eXP40-TTE, eXP40(60)-TTA/TTB

Items Items Items
Front Part 1) Analog Touch Panel: Input by user’s touch
2) LCD: Screen indication
Power status LED Indicating the state of device (On: BLUE)
USB Device 1) Logging/Recipe/Screen Data Backup
2) Send project data and XP-Run time
3) Receive back data and project file
Panel Mounting Part Fixing XGT Panel on the panel using bracket
USB Host 1) USB Memory Connection: Backup of data such as alarm/logging/recipe
and storage of screen data, Send/Receive project data, Send XP-Runtime
2) User’s Interface Connection: Using mouse/keyboard
3) Printer connection: Printing function
* Rated 5 VDC, Typical 100mA

 

Chapter 2 System Configuration

2-4

Items Items Items
Battery Cover <Setting Switch Configuration >

NO.1 A Config. Backup Battery ON
B Config. Backup Battery OFF
NO.2 A Config. Do not use
B Config. Do not use
NO.3 A Config. COM1 RS-485 Terminating Resistance On
B Config. COM1 RS-485 Terminating Resistance Off
NO.4 A Config. COM3 RS-422 Terminating Resistance On
B Config. COM3 RS-422 Terminating Resistance Off
NO.5 A Config. O/S Download Mode
B Config. Operating Mode
Power Terminal Composed of Power Input(DC24V) and FG Terminal
Ethernet Terminal Ethernet: 10Base-T/ 100Base-TX
1) Send Project Data
2) Receive backup data and project file
3) Send XP-Runtime
4) PLC/Control Device Communication
COM3 Connector RS-422/485: PLC or Control Device Communication
COM1, COM2
Connector
RS-485, RS-232C: PLC or Control Device Communication

 

Remark
(1) For further details on connection of communication, please refer to Communication Instruction Manual.
(2) For further details on installation, please refer to the Chapter 10.

 

A. Reset Switch
B. Coin Battery
C. Setting Switch

 

Chapter 2 System Configuration

2-5
2.2 System Configuration
In order to use XGT Panel, it is necessary for XP-Builder to prepare project data and transmit it to XGT Panel.
Normally you can connect with XGT Panel using RS-232C.
Maximum Communication speed is 115,200[bps].
With Ethernet in use, you can transfer project data more quickly.
With LAN environment built in the following configuration, you may use it more easily and effectively
1:1 connection will be supported just in case LAN environment is not built.

Chapter 2 System Configuration

2-6
If it is impossible to transfer project data using Communication, you can use USB storage device.
For how to use in details, please see the Chapter 7 and XP-Builder User’s Manual.

Remark
(1) Recommend to transfer project by using Ethernet than RS-232C.
(2) For how to make Ethernet cable, please see the Communication User’s Manual.
(3) For how to transfer project, please see XP-Builder User’s Manual.
(4) eXP40-TTE is not support Ethernet.

 

Chapter 3 Standard Specification

3-1
Chapter 3 Standard Specification
3.1 General Standards
XGT Panel general standard is as follows.

No. Category Standard Related
standard
1 Ambient
operating
temperature
0+50 -
2 Storage
temperature
-20+60 -
3 Operating
humidity
1085%RH, non-condensing. -
4 Storage humidity 1085%RH, non-condensing. -
5 Vibration
resistance
Occasional vibration count -
Frequency Acceleration Amplitude 10 times each in X,
Y and Z direction
IEC 61131-2
5≤f< Hz - 3.5mm
9≤f≤150 Hz 9.8m/s2 -
Continuous vibration
Frequency Acceleration Amplitude
5≤f< 9 Hz - 1.75mm
9≤f≤150 Hz 4.9m/s2 -
6 Shock
endurance
* Maximum shock acceleration: 147m/s2 (15G)
* Duration time: 11
ms
* Pulse wave: half sine pulse (3 times each in X, Y and Z directions)
IEC 61131-2
7 Noise
Immunity
Square wave
Impulse noise
DC: ±1,200V LSIS Standard
Electrostatic
Discharge
Immunity
±6 kV(Contact Discharge),
±8 kV(Air Discharge)
IEC 61131-2
IEC 61000-4-2
Electromagnetic
Radiated
Emissions
80 ~ 1,000 MHz, 10 V/m IEC 61131-2
IEC 61000-4-3
Electrical Fast
Transient & Burst
Immunity
Category Power module Communication
Interface
IEC 61131-2
IEC 61000-4-4
Voltage 2.4 kV 1.2 kV

 

Chapter 3 Standard Specification

3-2

8 Environment Free from corrosive gases and excessive dust -
9 Operating height Up to 2,000m(6,562ft) -
10 Pollution degree 2 or less -
11 Cooling method Natural Air-Cooling -

 

Remark
(1) IEC(International Electro technical Commission)
- International private group facilitating international cooperation of electric/electronic standardization,
issuing international standards and operating the compliance evaluation systems.
(2) Pollution degree
- As an index representing the pollution degree of an environment to determine the insulation of a device,
pollution degree 2 generally means the status generating non-conductive contamination. However, it also
contains the status generating temporarily conduction due to condensation.
(3) Definition of Overvoltage Categories
- Equipment of overvoltage category II is energy-consuming equipment to be supplied from the fixed
installation.
- Examples of such equipment are appliances, portable tools and other household and similar loads.

 

Chapter 3 Standard Specification

3-3
3.2 Function Standards
eXP Series function standard is as follows.

Item eXP20-TTA eXP40-TTE eXP40-TTA eXP60-TTA
Display type TFT color LCD
Screen size 10.9cm(4.3”) 17.8cm(7”) 25.9 cm(10.2”)
Display Resolution 480 x 272 800 x 600 pixel(WVGA)
Color indication 24-bit Color(16.7M) 16-bit Color(65,536)
Indication degree Left/Right:60 deg.
Upper:40 deg.
Lower:60 deg.
Left/Right:55 deg.
Upper:35 deg.
Lower:55 deg.
Backlight LED Type (Supports backlight auto-off function)
Backlight duration 30,000 hours 20,000 hours
Brightness 550cd/m2 230cd/m2 200cd/m2
Touch panel 4-Wire Resistive, analog
Audio Output Magnetic buzzer (85dB)
Process i.MX283(454MHz)
Memory Flash 128MB
Operating RAM 64MB
Backup RAM 128KB
Backup data Date/Hour data, Logging/Alarm/Recipe data and nonvolatile device
Battery duration Approx. 3 years (Operating ambient temperature of 50)
RTC Time error Approx. 3 sec/1day(Operating ambient temperature of 25)
Ethernet 1 channel,
IEEE802.1a, 10Base
T/100Base-TX
- 1 channel, IEEE802.1a, 10Base-T/100Base
TX
USB Host 1 channel, USB 2.0 Host (mouse, keyboard, printer and USB memory driver is available)
USB Device - 1 channel, USB 2.0 Device (for download and upload project file)
RS-485, RS-232C 1channel, RS-232C
(DSUB 9/Male Type)
2channels, RS-485, RS-232C (DSUB 9/Male Type)
RS-422/485 1channel, RS-422/485
(DSUB 9/Male Type)
1channel, RS422/485 mode (Terminal Type)
Multi-language Up to 12 language simultaneously
Animation GIF format is available
Recipe available
Data logging available
Script executor available
Certifications CE, UL(cUL), KC
Protection standard IP65
Dimension (mm) 128x102x32
(±0.2)
208.0 x 154.0 x 44.4
(±0.2)
276.0 x 218.0 x 44.4
(±0.3)
Panel cut (mm) 119.0x93.0 192.0 x 138.0 260.0 x 202.0
Rated voltage DC24V
Power consumption (W) 7W 23W 23W 23W

 

Chapter 3 Standard Specification

3-4

Item eXP20-TTA eXP40-TTE eXP40-TTA eXP60-TTA
Weight(Kg) 0.3 0.62 0.63 1.08

 

Note
(1) Caution in power connection
: With AC power applied to DC power device, it may cause product damage or fire.
Please pay a special attention to connection.
(2) PE Connection
: For the device PE, please use
PE terminal in the Chapter 2.1.
(3) Battery discharge-prevention DIP switch
: In order to prevent the battery discharge, turn off the DIP switch No.1.
To use backup function, please turn on DIP switch No. 1.
(4) Battery Operation and Life
: Battery is used for RTC (date/time) when the power of device is off.
Battery is not consumed with power applied.
(5) LCD Backlight Replacement
: Please replace LCD if you want to replace LCD backlight.
(6) Protection standard
: XGT Panel is designed by IP65 Standard in front parts. Ingress Protection (IP) is based on the IEC 60529
Standard for degrees of protection provided by enclosures. But XGT Panel does not guarantee from all
installation environment. When installing panels, make sure that dust and moisture are not brought in. For
more details on installation, See Chapter 10.installation and Wiring.

 

Chapter 4 System Configuration

4-1
Chapter 4 System Configuration
It describes the system configuration including XGT Panel’s time setting, Ethernet connection setting, and
Backlight settings.
If you press [Settings] button in XGT Panel’s Main screen, you can set XGT Panel’s environment as follows.
[Main screen]
[System Configuration screen]

Chapter 4 System Configuration

 

4-2

4.1 Backlight Setting
If you press [Backlight Setting] button in [System Configuration] screen as follows, setting screen shows up.
[Dialog box setting option]

Name Description
Brightness It may adjust brightness of backlight.
Do not turn off backlight It doesn’t turn off backlight power.
Turn off backlight after idle time It automatically turns off backlight if not in touch for a certain period of
time.
Turn off ~ minutes It turns off backlight after a designated time (unit of minute).

 

Chapter 4 System Configuration

4-3
4.2 Touch Calibration
When the location is not recognized in XGT Panel, Touch’s scale can be adjusted in XGT Panel. If you press
[Touch Calibration] button in System Configuration, the setting screen shows up. If you press five ‘+’ marks, XGT
Panel’s touch location adjustment is completed.

Remark
(1) XGT Panel’s Touch Calibration setting is basically set. If Touch location is way off, adjusting menu with
touch can be hard through touch. In that case, You can select the Touch Calibration setting menu by
USB mouse or simply touch
5 times at the empty space on the main screen.
(2) When touch location changes in using, redo touch setting.

 

Chapter 4 System Configuration

 

4-4

4.3 Date Time Setting
If you press [DateTime Setting] button in [System Configuration] as follows, you can set XGT Panel’s data and
time.

Remark
You can set data/time at device information of communication dialog at the XP-Builder.
For details, please refer to the XP-Builder’s manual.

 

Chapter 4 System Configuration

4-5
4.4 Environment Setting
If you press [Environment Setting] button in [System Configuration] screen as follows, you can set ‘Auto Goto
Screen’ and ‘Buzzer On/Off’.

Chapter 4 System Configuration

 

4-6

[Environment setting screen]

Chapter 4 System Configuration

4-7
[Dialog box setting options]

Name Description
Go to screen after boot up When setting [Auto Goto Screen], XGT Panel is rebooted. Or when downloading
the edit data is completed, the screen automatically shows up. If you cancel this
setting, the user should press ‘Start’ button in order to move to the screen.
Quick start When starting screen, screen shows promptly without showing progress bar
because it doesn’t caching the image in advance. However, if you select this
option, first screen shows slowly. Especially, if there are many animation objects
in screen, it may take several seconds based on image. But fast screen
switching is available since second screen switching.
Show progress
on the bottom
If XGT Panel start monitoring by touching the [Start] on the main screen, and the
buffering images used in your project. You will see the progress of the job. (If
you do not show the quick start setup.). In this case, if the [Show progress on the
bottom] check box is checked while this progress is displayed at the bottom of
the screen to a more simplified state. If you used the default screen background
image, you can try to apply this option.
Show always title bar
of popup window
It indicates title bar on pop up window. With title bar of pop up window selected,
it may move the location.
Do not show menu bar The menu bar basically provided to go out from monitoring screen to the waiting
screen doesn’t show. In this case, if you want to go out to the waiting screen,
you have to use the special switch to close the monitoring screen.
Enable Arabic text
display(right -> left)
It enables the language indicated from right to left directions.
Set startup screen The screen that corresponds to the number entered at the start of the monitoring
is displayed first.
Hide mouse cursor After the screen has been moved to another page, the mouse cursor does not
appear.
Buzzer On/Off You can set whether you use buzzer through [Buzzer On/Off] button.
Buzzer Test It may test the buzzer.
Reset USB Power
after boot up
When XGT Panel starts, USB power state is converted from Off to On initializing
the connected device.
Low Memory Mode XGT Panel screen to increase the operating speed, will use the images used on
the screen prior to the start of monitoring in advance, and then loaded into
memory. However, if the image of a very large amount of projects used, due to
the memory space constraints will not be able to load all the images before
monitoring begins. In this case, when the switching screen is performed, it will
take time for loading images and retrieving to search the memory and to delete
them that had not loaded at the beginning of the part. This kind of process may
XGT Panel make slow.
In this situation, we recommend that you use a "Low Memory Mode" by selecting
on the “Not use of image cash”. if you use "Low Memory Mode" rather than
loading the image prior to monitoring, it requires less memory by reducing time
for the loading the original images into the memory and deleting them in the
project. Consequently the performance can be improved.

 

Chapter 4 System Configuration

 

4-8

 

Clear SRAM memory and
data files
All files downloaded by the user are deleted. If connection password is set, you
have to input the password. This password is connection password needed for
project download, etc.
You can set that password in [Communication]
[XGT Panel Information]
[Password] tap.
The deleted files are user project file, web server, VNC start module, option card
driver, RAPIEnet communication setting data, XP-manager setting data and etc.
Setting through Environment Setting menu of device is not initialized. If the menu
is not in English, it is necessary to reboot device to delete the multilingual related
files.
Set Background Image If you select the image through [Set Background Image], background image of
waiting screen is set as the selected image. If you want to cancel, press [Delete
Background Image]
[Background Image Selection Screen]
[Use boot image] With an option selected, you cannot use it unless it is the
image of different resolution from that of XGT Panel or 24-bit image.

 

Chapter 4 System Configuration

4-9

Printer Settings If there is no printer information displays the following message and must be
downloaded from the XP-Builder. You can prepare your download, then go to
the Start menu in XP-Runtime and use the menu after using the printer settings
from XP-Builder.
<Printer driver and Information None
Download Required>
<The printer driver is ready to use>

 

Chapter 4 System Configuration

 

4-10

 

Printer Settings
(Dialog)
Name Description
Port Displays the connection type.
Printer type Displays the type of printer.
Print direction Sets whether horizontal or vertical.
Print color Sets whether color or black and white.
High quality print Specifies whether the advanced printing.
More... More Properties: Displays additional properties. If
you change the additional printer properties, check
the information in the dialog. After that, press the OK
button to save settings.
OK To save the settings.
Cancel To cancel the setting.
Printer Check To diagnose the connection status of the printer. This
feature is only supported Sewoo printer (LK-P30, LK
P41, LK-P43). Press the button to display the current
printer status. Please mount again the printer cable if
the printer is already powered with the cable
connected.
*Messages*
1. OK: Normal state
2. No Printer: Not connected to the printer
3. Cover Open: Paper cover is open
4. Paper Empty: Out of paper
Test Page This function is designed to test the print output
status. Outputs the following information, and it
briefly shows the current print stat.
***********************************
Test page
***********************************
DateTime: 2014-02-04 10:00:00
XP-Runtime version: 1320
Printer driver version: 1.00
Printer name: PCL3 LaserJet
Port: USB
***********************************

 

Chapter 4 System Configuration

4-11
4.5 Ethernet Setting
If you press [Ethernet Setting] button in [System Configuration] screen as follows, you can change IP to use
Ethernet.
You can change IP address by pressing [Set] button of each IP address, Subnet Mask and Gateway. By
pressing OK button, changed IP information is reserved.

Remark
We recommend the following method, when connecting with PC solely.

If you reboot after pressing [Disable] button, the device will not use Ethernet. In this case, booting speed gets
faster.
If you use Ethernet again, reboot after pressing [Enable].
1) XGT Panel setting
- IP Address : 192.168.0.10
- Subnet Mask: 255.255.255.0
- Gateway : 192.168.0.1
2) PC setting
- IP Address : 192.168.0.11
- Subnet Mask: 255.255.255.0
- Gateway : 192.168.0.1

Chapter 4 System Configuration

 

4-12

4.6 XP-Remote Setting
Settings of XP-Remote that can remotely adjust XGT Panel can be changed.
[XP-Remote Setting Screen]
[Dialog box setting options]

Name Description
Allow XP-Remote to connect It allows connecting remote XP-Remote.
Max. of XP-Remote
connections
It designates the maximum number of XP-Remote connected with XGT
Panel.
Timeout value It stops communication when there is no request of communication from
XP-Remote within the designated time. In case XP-Remote is entitled to
manipulation, it withdraws the right to manipulation
(10 seconds ~ 300 seconds)
Enable control by XP-Remote
after Monitor Start
XGT Panel, will automatically allow state control after the monitor was
started.

 

Note
For the function of XP-Remote in detail, please refer to XP-Remote user’s manual.

 

Chapter 4 System Configuration

4-13
4.7 Buzzer Setting
It may adjust volume and height of XGT Panel Buzzer.
[Buzzer Settings Screen]
[Dialog box setting option]

Name Description
Buzzer On It may turn on or off the buzzer that occurs when in touch mode
Buzzer volume It may adjust the volume of Buzzer
Buzzer tone It may adjust the tone of Buzzer.

 

Chapter 5 Diagnostics

5-1
Chapter 5 Diagnostics
It describes the diagnosis function for XGT Panel’s communication terminal, screen and touch function.
If you press [Diagnostics] button on the XGT Panel’s basic screen, the menu for diagnosis shows up.
[Main Screen]
[Diagnostics setting screen]

Chapter 5 Diagnostics

 

5-2

5.1 Screen Diagnosis
If you press [Screen] button, screens continuously change into diverse color with buzzer. After all screen for
diagnosis pass. Then, Close button shows up with white ground.
If you press Close button, the initial screen shows up.
[Diagnosis screen]
[Screen diagnosis]

Display Sequence RED > GREEN > BLUE > BLACK > WHITE>GRAPH

 

Chapter 5 Diagnostics

5-3
5.2 Touch Diagnosis
If you touch the screen, the touched location is displayed as follows. If pressing the [OK] button, you can quit
the screen.
If the touched location is not correct, reset the Touch setting. For detailed information, please refer to the
Chapter 4.2 Touch Calibration.
Touch diagnosis

Chapter 5 Diagnostics

 

5-4

5.3 Backup Memory Diagnosis
If you press [Backup Memory] button, you can see the result of diagnosis in the result windows.

Remark
(1) If ‘NVRAM Data Access … Fail’ error is occurred, please contact with customer service center.
(2) If ‘BATTERY STATUS … BAD’ error is occurred, battery should be changed. Please contact with
Customer service center.
If the DIP switch No.1 is set up as B, please set it up as A. The ‘B’ is the mode in which the backup
battery is not used.

[Completion of Backup Memory diagnosis]

Chapter 5 Diagnostics

5-5
5.4 Flash Memory Diagnosis
If you press [Flash Memory] button, you can see the result of diagnosis in the result widows.

Remark
If ‘Read Disk Information Error!’ occurs, please contact with Customer service center.

[Completion of Flash Memory diagnosis]

Chapter 5 Diagnostics

 

5-6

5.5 USB Memory Diagnosis
If you press [USB Memory] button, the result of diagnosis shows up in the result windows.

Remark
If ‘Read Disk Information Error!’ occurs, remove it first and test it after inserting it again.
If the error message shows up repeatedly, please contact with customer service center.

[Completion of USB Memory diagnosis]

Chapter 5 Diagnostics

5-7
5.6 Serial Communication Diagnosis
If you press [Serial] button, you can diagnose Serial ports which is equipped at XGT Panel.
(In case of diagnosis purpose, you have to connect the loop-back terminal at each port.)
[Serial port selection]
[Completion of serial port diagnosis]

Chapter 5 Diagnostics

 

5-8

The RS-232C port terminal should be made as follows. (Connect the No.2 and 3 pin)
The RS-485 and RS-422/485 port terminal should be made as follows. (Only eXP40/60)
- Connect the RS-485 No.1 with RS-422/485 No.2 and No.4
- Connect the RS-485 No.6 with RS-422/485 No.1 and No.3
eXP20-TTA/DC does not provide for the communication diagnostics of RS-485/422 communication.

Chapter 6 Viewing Information of PLC Connection Status

6-1
Chapter 6 Viewing Information of PLC Connection Status
PLC Information, it shows XGT Panel configuration, PLC CPU status and various records.

Remark
You can check the status of PLC connection after project data is transmitted into XGT Panel.

 

Chapter 6 Viewing Information of PLC Connection Status

 

6-2

6.1 PLC Communication Configuration Settings
You can select [Settings] button to change PLC communication settings
[PLC Communication Configuration setting]

Remark
- PLC Communication Configuration setting dialog box may look different depending on drivers.
- For further information about the settings, please refer to the PLC user manual.

 

Chapter 6 Viewing Information of PLC Connection Status

6-3
6.2 Connection Information
You can check the setting items for the connection with PLC such as vender of PLC, target device, connection
type, ip address, connection information and timeout value in the XP-Builder.
[Dialog box Description]

Name Description
Connection No. The communication connection No. is displayed from No.0-15.
Vendor The vendor of the communication target device is displayed.
Target device The communication target device is displayed.
Connection type The connection type is displayed
Timeout value The set-up timeout value is displayed.
Send wait value The transmission wait value is displayed.
Retry value In case when timeout occurs during communication, the retry value is
displayed.

 

Chapter 6 Viewing Information of PLC Connection Status

 

6-4

6.3 PLC Information
You can check CPU type of PLC, operation mode, state, version, and scan time.

Remark
The following PLC is available for view of PLC information.
- MASTER-K CPU, FEnet, Cnet
- GLOFA-GM CPU, FEnet, Cnet
- XGK/XGB/XGI/XGR CPU, FEnet, Cnet

6.4 History of PLC Error
You can check the PLC Error History.

Remark
The following PLC is available for viewing Error History.
- MASTER-K CPU doesn’t have the Error History.
- GLOFA-GM CPU, FEnet, Cnet
- XGK/XGB/XGI/XGR CPU, FEnet, Cnet

 

Chapter 6 Viewing Information of PLC Connection Status

6-5
6.5 History of PLC Mode Conversion
You can check the history about our PLC’s RUN/STOP operation mode.

Remark
The following PLC is available for viewing PLC operation mode conversion history.
- MASTER-K CPU doesn’t have the history about operation mode conversion.
- GLOFA-GM CPU, FEnet, Cnet
- XGK/XGB/XGI/XGR CPU, FEnet, Cnet

6.6 History of PLC Power
You can check the history about when PLC was turned on and off

Remark
The following PLC is available for viewing the history of when our PLC was turned off and on.
- MASTER-K CPU doesn’t have the history about when our PLC was turned on and off.
- GLOFA-GM CPU, FEnet, Cnet
- XGK/XGB/XGI/XGR CPU, FEnet, Cnet

 

Chapter 6 Viewing Information of PLC Connection Status

 

6-6

6.7 History of PLC System
You can check history about PLC system.

Remark
The following PLC is available for viewing history about system.
- MASTER-K CPU doesn’t have the history about system.
- Only GLOFA-GM CPU (GM4C) has the history about system. Other CPUs don’t have the history about system.
- XGK/XGB/XGI/XGR CPU, FEnet, Cnet

 

Chapter 6 Viewing Information of PLC Connection Status

6-7
6.8 N:1 Settings
Using N:1 communication, it means communicate number of XGT Panel with single PLC.
[N:1 settings dialog box]
[Dialog box setting options]

Name Description
Use N:1 Communication The matter of performing N:1 communication is designated.
N:1 station number The station number of N:1 communication is input.
Number of XGT Panel The number of XGT Panel in N:1 communication is input.
Master Holding Time The master holding time of N:1 communication is input.

 

Remark
For detail information about the N:1 communication, please refer to the XP-Builder manual.

 

Chapter 6 Viewing Information of PLC Connection Status

 

6-8

6.9 Program Monitor
The programs that adopt LD language of XGK series can be monitored.

Remark
- Program Monitor driver can be downloaded from XP-Manager.
- Only support for XGK/XGB CPU, Cnet, Enet communication
- To enable the [Program Monitor] button, program monitor should be checked in which locates in the XP
Builder project
property menu.

 

Chapter 7 Storage Function

7-1
Chapter 7 Storage Function
7.1 General Introduction
Downloading the user project made in XP-Builder from PC, uploading the project stored in the device to PC,
updating the device and etc are available through connection with XGT Panel with Serial cable or Ethernet cable
generally. However, when those connections are not available, you can use USB storage equipment
1. If you touch [Storage Function], the following dialog box shows.
2. In case of downloading the project by using USB storage equipment, touch [Project Download] button.
3. In case of transmitting the project data stored in the device to USB storage equipment, touch [Project
Upload] button.
4. In case of updating the XGT Panel with XGT Panel Software stored in USB Storage equipment, touch [XGT
Panel Update] button.

Chapter 7 Storage Function

 

7-2

7.2 Downloading Project through the Storage Equipment
1. If you touch [Project Download], the following dialog shows.
2. Please select the targeted external memory in “Select Source”. Following path is indicated depending on the
selected external memory.
- USB: USB StorageXP_Project
In case of downloading the project by using storage equipment, the project should be saved in the one lower
directory between those directories.
3. Select one among directory lists and touch [OK].
4. Touch [OK] button, then download is started.

Chapter 7 Storage Function

7-3
7.3 Uploading Project through the Storage Equipment
1. If you touch [Project Upload], the following dialog shows.
2. Please select the targeted external memory in “Select Source”. Following path is indicated depending on the
selected external memory
- USB: USB StorageXP_Backup
3. If you touch [OK] button, project backup file is transmitted to the selected path.
4. The project backup file is saved when Download project backup file is selected when downloading the
project.
If you don’t select, project backup file is not saved in the device and transmission to the storage equipment is
not available.

Chapter 7 Storage Function

 

7-4

7.4 Updating the Device through Storage Equipment
1. If you touch [Project Upload], the following dialog shows.
2. Please select the targeted external memory in “Select Source”. Following path is indicated depending on the
selected external memory
- USB: USB StorageXP_Software
In case of updating the device by using storage equipment, the XGT Panel Software project should be
saved in the one lower directory between those directories.
3. If you touch [OK] button, the device is updated with XGT Panel Software in the designated path.

Chapter 8 XGT Panel S/W Update

8-1
Chapter 8 XGT Panel S/W Update
8.1 General Introduction
It describes the function for updating the XGT Panel software.
Basically you can optimize XGT Panel when you download the project file in XP-Builder. Please use this function
only in case of updating XGT Panel specially.
New function is added to XGT software, you need to update a version of XGT Panel.
Please refer to the following.
[Method]
Select [Upgrade -> Update XGT Panel] on the XGT Panel’s main screen. Then XGT Panel becomes update
mode. In order to return to the main screen, touch a “MENU” button or touch the screen for 3 seconds
After downloading XGT Panel software from LSIS website, make a temporary folder and save it.
Designate the folder where the software will be saved in the XP-Builder’s [XGT Panel Update] windows and
update XGT Panel by [Send] menu. For more detailed information about XP-Builder, please refer to the XPBuilder user manual.

Remark
Do not remove communication cable or turn off the device during updating.
It may cause the abnormal operation.

 

Chapter 9 File Backup through External Storage Equipment

9-1
Chapter 9 File Backup through External Storage Equipment
Describes on management function about external storage equipment saving backup data of logging, recipe,
and screen image
(1) XGT Panel can back up the logging, recipe, and screen image data at USB storage equipment according to
setting in XP-Builder.
(2) In case there is no space for backup in the designated storage equipment, it continues backup deleting
previous data or stops backup according to setting in XP-Builder
(3) Monitors attachment status of backup equipment at XP-Builder.
9.1 Path Structure in case of File Backup
Backup path structure of logging, recipe, and screen image is as follows.
Logging
YYYY.MM.
BeginDay.EndDay.0
DD.
BeginHour.EndHour.0 (space for one folder is full)
HH.
BeginMinute.FF
Lhhmmss0.CSV
Recipe
Rhhmmss0.CSV (same as lower structure of each logging number)
DD.
BeginHour.EndHour.1
DD.
BeginHour. FF (There is free space for one folder)
1 (Logging Number)
2 (same as lower structure 1)
ScreenImage
Shhmmss0.BMP (same as lower structure of each logging number)
Root directory of CF or USB storage equipment
1. Path structure in case of logging backup
(1) Directory named ‘Logging’ is created under the root directory of USB equipment
(2) The directory whose name is logging number is created under Logging directory.
(3) The directory whose name is year, month is created under Logging number directory.
(a) Includes day directory under
(There is free space for one folder)

Chapter 9 File Backup through External Storage Equipment

 

9-2

(b) Up to 500 day directories can be created.
(c) Name of year, month directory includes the firstly created day information under its directory
Ex) In case directory is created in 2010, October and includes directory since 15th under, directory’s name
is
: 2010.10.15.FF
FF at end means the directory can save more data created in 2010, October (currently, the number of
lower directory is 500 or less)
(d) In case month is changed, changes directory name to day information of last created day directory.
Ex) In case month becomes November from October and directory from 15th directory to 30th have been
created in 2010, October directory.
: 2010.10.15.30.0
(e) Though month is not changed, in case the number of day directory under year, month directory is 500 or
above, directory name is changed into name including day information of last created day directory.
Ex) In case the number of directory from first to 15th is 500 or above in the directory created in 2010,
October.
: 2010.10.01.15.0
(f) In case there is the year, month directory having same start day and end day when changing directory’s
name due to over 500 day directories or change of month, last digit index number increases.
Ex) In case there are three year, month directories that are having over 500 day directories created in
October first and 2010 year October directory
: 2010.10.01.01.0
: 2010.10.01.01.1
: 2010.10.01.01.2
(4) Day directory is created under year, month directory
(a) Hour directory is created under day directory
(b) Day directory can have up to 500 hour directory
(c) Name of day directory includes not day information but also hour information of first created hour
directory
(d) Relation between day directory and hour directory is same as relation between year month directory and
day directory.
(5) Directory whose name includes hour information is created under day directory.
(a) Hour directory includes backup file under
(b) Hour directory can include up to 500 backup file
(c) Name of time directory include not only hour information but also minute information of first created file
under
(d) Relation between hour directory and backup file is same as relation between year, month directory and
day directory.
(6) Name of logging backup file includes the created hour, minute, second information.
(a) Backup file is created in CSV format.
(b) File name start with ‘L’ meaning logging and includes hour, minute, second, index information
(c) In case backup file is created at the same time in terms of second, index information at the end of file
name increases.
2. Path structure in case of recipe backup
(1) Directory named ‘Recipe’ is created under USB storage equipment root directory.
(2) Year, month directory is created under Recipe directory
(3) The lower directory structure is same as that of logging backup path structure.
(4) Name of recipe backup file includes the created hour, minute, second information.

Chapter 9 File Backup through External Storage Equipment

9-3
(a) Backup file is created in CSV format.
(b) File name start with ‘R’ indicating recipe and includes hour, minute, second, index information.
(c) In case backup file is created at the same time in terms of second, index information at the end of file
name increases.
3. Path structure in case of screen backup
(1) Directory named ‘Screen Image’ is created under USB storage equipment root directory.
(2) Directory whose name is year; month is created under Screen Image directory.
(3) The lower directory structure is same as that of logging.
(4) Name of screen image backup file includes hour, minute, second information.
(a) Backup file is created in bitmap format.
(b) File name starts with ‘S’ and includes hour, minute, second, index information.
(c) In case backup file is created at the same time in terms of second, index information at the end of file
name increases.
4. Structure of path at memo backup
(1) ‘Memo’ directory will be formed at the sub route directory of USB storage device.
(2) Directory in the name of Year and Month will be formed below the Memo Directory.
(3) Structure of directory thereafter is same as that of logging backup route.
(4) Memo backup file has the name made of hour/minute/second when it was created.
(a) Backup file is created in the type of bitmap.
(b) File name starts with ‘M’ that represents the screen image, which includes the index information of hour,
minute, and second thereafter.
(c) In case backup file is created at the same time up to second, it increases the far end index information.
5. Structure of path at live image recording
(1) ‘Movie’ directory will be formed at the sub route directory of USB storage device.
(2) Recorded live image is stored below the Movie Directory.
(3) Live image file has the name made of year/month/date/hour/minute/second information when it was
created.
(a) Backup file will be created in AVI type. H.264 and Mp3 were used for Video CODEC and Audio CODEC
respectively.
(b) File name starts with ‘MOV’ that represents screen image, which includes data and hour information
thereafter.
(c) Live image can be stored up to the number 1,000 files. This number can be designated at the special
device settings of XP-Builder.
6. Structure of path when Blue Screen of camera image and live image is created
(1) ‘MovieStill’ directory will be formed at the sub route directory of USB storage device.
(2) Recorded live image will be stored below MovieStill directory.
(3) Blue screen image file has the name made of year/month/date/hour/minute/second information when it was
created.
(a) Backup file will be created in JPG type.
(b) File name starts with ‘STL’ that represents screen image, which includes data and hour information
thereafter.
(c) Live image can be stored up to 1,000 files. This number can be designated at the special device settings
of XP-Builder.

Chapter 9 File Backup through External Storage Equipment

 

9-4

 

Remark
(1) When changing device time, in case of changing current time into after time, we guarantee the normal
operation. But in case of changing current time into early time, we don’t guarantee the normal operation.
In this case, you have to delete directory including the changed hour and its lower directory for normal
operation. For example, if you change time from December 10
th to December 5th, you have to delete
year, month directory created in December 10
th and restart the device
(2) Sorting by project is not supported for each logging, recipe, screen image. For example, there are no.1,
2, and 3 logging groups in the project A. And in case each logging group backups the file, 1, 2, 3
directories are created and each data is saved under each directory. Then, in case file backup occurs in
the project B having no.1, 2 logging group, backup file is created in same directory of project A. In this
case, you have to sort the backup files of project A and B based on the created time.

 

Chapter 9 File Backup through External Storage Equipment

9-5
9.2 Operation setting when there is no space for backup
You can designate in the XP-Builder whether to cancel the backup or delete the oldest backup file and execute
backup when there is no space in the storage equipment.
[Project Property Setting -> Storage Settings -> Backup Storage -> Delete old file if disk full]
1. In case of backup, deleting the oldest data
(1) In case there is no space for backup, searches the oldest year, month directory under Logging, Recipe,
Screen Image. (But in case of Logging, finds under Logging number directory. That is, when executing
backup about Logging number 2, in case there is no backup data in Logging number 2 directory and there
is data only in logging number 1, data of logging number 1 is not searched/deleted.)
(2) Searches the oldest day directory under the oldest year, month directory.
(3) Searches the oldest hour directory under the oldest day directory.
(4) Deletes the oldest backup file under the oldest hour directory.
(5) Checks the space and if more space is necessary, the above steps of (1) ~ (4) are repeated and checks
the space.
(6) When deleting file, in case all data in time directory are deleted, relevant hour directory is deleted.
(7) When deleting hour directory, in case all hour directories in day directory are deleted, relevant hour
directory is deleted.
(8) When deleting day directory, in case all day directories in year, month directory are deleted, relevant year,
month directory is deleted.

Remark
(1) In unknown directory or file (user file or directory), searches the oldest thing among normal backup files
except unknown directory or file.
(2) In case there is nothing except user data in now searched directory, backup operation fails. XGT Panel
can’t delete user data, at this point, operation stops.

 

Chapter 9 File Backup through External Storage Equipment

 

9-6

9.3 Monitoring Connection Status of External Storage Equipment
XGT Panels monitors connection status about external storage equipment designated when setting backup path
in XP-Builder.
The following figure is backup path specified in XP-Builder.
In order to use this monitoring function, you have to set about system alarm window, and then the project should
be downloaded.

Chapter 9 File Backup through External Storage Equipment

9-7
In case USB storage equipment is removed during operation after setting the path for saving Logging backup file
as USB storage equipment and downloading the project into device, the designated system alarm (HS951.0) is
set. In case storage equipment is equipped again, alarm is reset.
In case USB storage equipment is removed during operation after setting the path for saving Recipe backup file
as USB storage equipment and downloading the project into device, the designated system alarm (HS951.1) is
set. In case storage equipment is equipped again, alarm is reset.
In case USB storage equipment is removed during operation after setting the path for saving Screen Image
backup file as USB storage equipment and downloading the project into device, the designated system alarm
(HS951.2) is set. In case storage equipment is equipped again, alarm is reset.
Internal address of the designated system alarm can be checked in XP-Builder as follows.

Chapter 10 Installation and Wiring

10-1
Chapter 10 Installation and Wiring
10.1 Installation
10.1.1 Installation environment
This machine has high reliability regardless environment. But for reliability and stability, be careful the followings
(1) Environment condition
(a) Install at the panel which can protect this machine from water and dust. XGT Panel is designed by IP65
Standard in front parts and IP20 Standard in rear parts.
(b) Install at the place where impact and vibration is not continuously applied. XGT Panel is designed to
meet IEC standard (IEC 61131-2).
(c) Do not expose this machine to direct light.
(d) Do not install at the place where rapid temperature change can occur. Moisture by rapid temperature
change can cause malfunction and damage.
(e) This machine should be installed within 0 ~ 50°C, otherwise the screen may be changed or cause
malfunction
(f) This machine should be installed within 10~85% relative-humidity. Moisture by rapid temperature change
can cause malfunction and damage.
(g) Avoid corrosive gas and burnable gas.
(h) Dry location use only.
(2) Installation construction
(a) When doing screw’s processing or wiring construction, be careful that the remains do not enter the XGT
Panel inside.
(b) Install at the place where you can easily control.
(c) Do not install with high voltage machine within same Panel.
(d) Keep distance of more than 100mm from duct for wiring and peripheral machine.
(e) Ground at the place where few noises develop.
(3) Anti-heat design of control panel
(a) In case of installing XGT Panel in the airtight panel, consider the heat by other machine as well as own
heat. In case that the air circulates through a ventilating opening or a general pan, XGT Panel system can
be influenced by in-draft of dust or gas.
(b) We recommend you to install a filter or to use an airtight heat exchanger.

Chapter 10 Installation and Wiring

 

10-2

Remark
(1) Waterproof & dustproof standards
(a) IP65 Standards
1) The protection standards of XGT Panel have been designed to meet the IP65 test conditions, in
accordance with the degrees of protection provided by enclosures of IEC60529.
As this machine installed at the panel, it is not guaranteed with all installation environment even though
its protection standards for the front parts are satisfied.
2) IP65 rating guarantees the enclosure is dust proof (6) and protected against jets of water (5).
3) IP20 rating guarantees protection from solid foreign objects of 12mm diameter and greater (2), but it
does not guarantee protection from water ingress.
(b) Notices
1) In the environment where the protection grade of XGT Panel is exceeded or not satisfied, the
damage of the device or malfunction can occur due to the failure of protecting the product.
2) Since the protection grade of XGT Panel is the waterproof/dustproof standards, it cannot be
protected from oil, corrosive gas and metal particles.
3) In case when Gasket is damaged by chemicals and continuous vibration, its waterproof/dustproof
effect can be weakened.
4) In case when installing the panel, make sure that dust and water are not brought in panels.

Chapter 10 Installation and Wiring

10-3
10.1.2 Notice in handling
It describes the notice from opening to installation.
Do not drop or cause heavy impact.
Do not disassemble voluntarily. When doing this, we are not responsible for the product.
When wiring, be careful that the remains do not enter into XGT Panel.
10.1.3 Notice in installing the panel
Here describes how to install XGT Panel in panel and notice.
(1) Panel cut
Before installing the XGT Panel in panel, panel should be made with the following dimension.

Classification X(Wide) Y(Height) Z(Thickness)
eXP20-TTA 119 1 93 1 1.6~9.5
0 0
eXP40-TTA(E) 192 1 138 1
0 0
eXP60-TTA 260 1 202 1
0 0

Unit: [mm]
X
Y
Z

Chapter 10 Installation and Wiring

 

10-4

(2) XGT Panel installation
Keep the distance of 100 mm between XGT Panel and panel per each direction.
Remark
(1) To be affected at a minimum by the electromagnetic waves (radial noise) or heat from other controllers,
it needs to keep its distance as the above explanation.
(2) When installing, consider the power and communication cable wiring.
(3) In case when the size of the panel cut exceeds the range of the standard allowance(0 ~ +1mm) when
producing panels, the contact area between Gasket and the panel can get small, which can weaken the
waterproof/dustproof effect.
When mounting the XGT Panel inside a panel, ensure that you use the gasket to protect against dust or
water ingress.

100

100

100
100

100
Unit: [mm]
Waterproof/Dustproof
Gasket

Chapter 10 Installation and Wiring

10-5
Remark
(1) Must be used the gasket to prevent dust or other contaminant ingress.
(2) When mounting at the panel, if the surface of panel is uneven, water or dust can enter the machine
through the gaps. As such problems can occur depending on the thickness and material (steel, aluminum,
acrylic and etc.) of the panel, it is required to review the installation environment. Also it is necessary to
check if Gasket and the panel are closely contacted together.
(3) When Gasket is contaminated or damaged by the deterioration after the use for a certain period of time,
the waterproof/dustproof effect can be noticeably weakened. In case when Gasket should be replaced,
contact the agency or a sales office close by.
(3) Installation location
When installing the XGT Panel, consider screen and use of touch.
When you don’t see within the following angle, you may not see clearly. When installing, consider angle.

Item Left and Right Upper Lower
eXP20-TTA 60 deg. 40 deg. 60 deg.
eXP40-TTA(E)
eXP60-TTA 55 deg. 35 deg. 55 deg.

(4) Fixation
Fix XGT Panel to the panel using the supplied brackets provided in the OEM packaging.
Affix Using
supplied brackets
Affix Using
supplied brackets
Panel Affix using supplied brackets
Affix using supplied brackets

Chapter 10 Installation and Wiring

 

10-6

Remark
(1) Remove the protection film attached to the front of this machine. Due to the deformation of the
protection film, the touch malfunction or wrong input can occur. It is recommended to use a special
protection sheet to protect the front sheet. In case of purchasing the protection sheet, contact the
agency or a sales office close by.
(5) Removal of protection film
The film attached to protect the front sheet when this machine has been released, should be removed after
it is installed in the panel.
Remark
(1) During installation, XGT Panel should be closely contacted to the panel not to have any gap. In the
environment requiring waterproof/dustproof effect, install and fix a bracket on a slope.
(2) The bracket should be fixed symmetrically(up-down, left-right). In case when it is not fixed symmetrically,
there could be a gap between the panel and XGT Panel.
(3) When fixing the bracket, it should be installed perpendicularly to the panel, and the required bracket
screw torque is 6.7±0.3kgf
cm. Depending on the material type of the panel, the torque value can be
different. The standard screw torque for each bolt size is followed. If it is fixed with the power more than
the required screw torque, the touch malfunction or weakening of waterproof/dustproof can happen due
to the deformation of XGT Panel.

Chapter 10 Installation and Wiring

10-7
10.2 Wiring
It describes the wiring that you should know when installing the XGT Panel.
10.2.1 Power wiring
eXP Panel is the DC product.

Power Name
DC 24V eXP20-TTA/DC
eXP40-TTA(E)/DC, eXP40-TTB/DC
eXP60-TTA/DC, eXP60-TTB/DC

► If AC power is applied into the product for DC power, It may cause damage or fire. Be careful
of connection.
► ‘/DC’ is the product which use DC 24V. When using the product, Please check the label
in the back of the product.
Warning

Chapter 10 Installation and Wiring

 

10-8

The power terminal should have the following specification.

Type Cable specification (Unit: ㎟)
Power and protection
ground
1.5(AWG16) ~ 2.5(AWG12)

Remark
(1) For installations where there is voltage drop, it is recommended to use stranded wire with a cross sectional
area greater than 2
.
(2) It is recommended that cable connections are twisted and secure. Short cable runs are also recommended
between the point of supply and the XGT panel.
(3) For safety reasons it is recommended that you use color coded outer sheaths on the conductors to aid safe
terminations.
Wiring of power is as follows.
[DC Power connection]
Remark
(1) Use a regulated power supply transformer when the power fluctuation is bigger than the standard.
(2) If electromagnetic interference is experienced or expected use an insulation transformer to protect the
XGT panel from interference.
(3) All field-wiring connections to this unit shall be from Limited Voltage/Limited Current, below 24V dc
isolated secondary source, Class 2 secondary circuits or SELV/PELV circuits.

Chapter 10 Installation and Wiring

10-9
Separate the XGT Panel power from the I/O device and main circuit device.
Remark
Separate the XGT Panel power supply cable from the main circuit cable (high voltage and current) and
input/output cable. Maintain a minimum separation of 100mmbetween cables.
Use a lightning surge protector to prevent damage from lightning strikes.
Remark
(1) Separate E1, the ground connection for lightning surge protector, and E2, the ground connection for
XGT Panel.
(2) Set lightning surge protector to below the allowable surge voltage to provide protection if the voltage
increases to its maximum.

E2
XGT Panel
E1

Surge absorber to prevent the lighting

Chapter 10 Installation and Wiring

 

10-10

Use an insulation shielding transformer or noise filter when the electromagnetic interference occurs.
Keep the stripped ends of the terminated cables twisted and as short as possible. When running the wiring avoid
running the cables for the insulation shielding transformer or noise filter pass through the cable duct.
When you use the magnetic lighting contactor (MC) for AC/DC, it is recommended to use a ferrite core close to
the power terminals as shown below.
10.2.2 Ground wiring
(1) Our XGT Panel has enough anti-noise measure, so except that there are many noises specially, the
ground is not needed. When you use the ground connection, refer to the following information.
(2) Use the exclusive ground connection. When you install the ground connection, use the third grounding
resistance (less than 100Ω).
(3) If you cannot use the exclusive ground connection, use the common ground connection like below.
A) Exclusive ground: Best B) Common ground: Good C) Common ground: Poor
(4) Use cables for grounding/earth connections by using cable with a cross sectional area greater than 2.0
.
Install the ground connection as close as possible to the XGT Panel.
Remark
Check and test the grounding connection. If the connection is bad or in case of (B) above, the XGT Panel
may malfunction or the communication signals may fail.

XGT

 

Other
devices

 

XGT

 

XGT Other
devices

3rd grounding connection 3rd grounding connection
Ferrite core
(CU1330B, E-TECH)
(CU1330G, E-TECH)
(ZCAT3035-1330, TDK)

Other
devices

 

Chapter 11 Maintenance

11-1
Chapter 11 Maintenance
To keep the XGT Panel best, examine the XGT Panel.
11.1 Maintenance
Because an error may be developed by environment, the periodic maintenance is needed. You should check the following
categories once or twice every 6 months.

Maintenance category Criterion Action
Power Within the power change range
(Within
-15% / +10%)
Modify the source of electric power in order to be in
the fluctuation range of a permissible voltage.
Environment Operating
temperature
0 ~ + 50 Modify the operating temperature and humidity to be
proper.
Operating
humidity
10 ~ 85%RH
Vibration No vibration Use the anti-vibration rubber and make a count
measure.
Getting loose of power terminal There is no unwinding Screw the unwound terminal.
Getting loose of
communication connector
There is no unwinding Screw the unwound terminal.
Reserved part Amount of reserved part and
reservation
Check the status
Refill the insufficiency and improve the reservation.
Gasket installation status No gap between the gasket and
panel.
Replace gasket or affix brackets firmly
Gasket status No damage or deterioration Replace gasket

11.2 Daily Maintenance
Check the followings daily.

Maintenance category Maintenance contents Criterion Action
Mounting status Check the brackets Should be mounted firmly Retighten screws
Power terminal status Loose terminal screws Not loose Retighten screws
Reduce the distance between
compressed terminals.
Keep the proper distance. Correction
Communication connector
status
Unwinding of fixed screw Not loose Retighten screws
Indication LED Check the lighting Blue LED should be turned on Refer to the appendix 1.

 

Chapter 11 Maintenance
11.3 Periodical Maintenance

11-2
Check the followings once or twice every six months and take measure.

Maintenance category Maintenance
method
Criterion Action
Environment Surrounding
Temperature
Measure through
Temperature
/Hygrometer Measure
of corrosive gas
0 ~ 50 °C Modify it to meet
the general standard.
(Environment standard
in the panel)
Surrounding
Humidity
10 ~ 85%RH
Surrounding
pollution degree
No corrosive gas.
XGT Panel
Status
Unwinding, swing Move XGT Panel Fixed firmly Retighten screws
Dust, foreign
matter adhesion
Visual check Not loose -
Connection
status
Looseness Retighten screw with
Screwdriver
Not loose Retighten screws
Reduce the distance
between compressed
terminals.
Visual check Keep the proper
distance.
Correction
Loose connectors Visual check Not loose Wind the fixed screw of
connector
Loose brackets Retighten screw with
Screwdriver
Not loose Retighten screws
Power voltage maintenance Check the power
voltage of input terminal
of power by test
AC100~240V: AC85~
264V DC24V: DC19.2 ~
28.8V
Supply
power modification
Battery Check when battery is
exchanged and voltage
drop is indicated.
(It is expressed
by system alarm)
Check the total of
power stoppage time
and guarantee
duration
There is no battery
voltage drop indication
If guarantee duration is
exceeded even tough
there is no battery
voltage drop indication,
change the battery.
LCD Backlight maintenance Visual check Check the guarantee
duration
When error occurs,
change the backlight.
Touch status Touch location error Check at the
Diagnostics
of XGT Panel
Appropriate
touch location
Reset at the setting of
XGT Panel.
Damage of Touch Visual check There is no damage
or deterioration
When error occurs,
change touch
Damage or Deterioration
of protection sheet
Visual check There is no damage
or deterioration
When error occurs,
Change protection
sheet

 

Chapter 11 Maintenance

11-3
Remark
(1) Battery exchange time is expressed by alarm. System alarm is expressed when system alarm category
is set at the XP-Builder as follows.
(2) Replace Battery With Hitachi Maxell, Part No. CR2032 Only. Use of Another Battery May Present A Risk
Of Fire or Explosion. See Owner's Manual For Safety Instructions.
WARNING: Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire.
(3) As the eXP model has the integrated LCD and backlight, the LCD should be replaced when the life is
over or it is out of order.

Chapter 12 EMC Standard Certification

12-1
Chapter 12 EMC Standard Certification
12.1 Requirement for EMC Standard Certification
EMC command is regulated on “It doesn’t produce the Strong electromagnetic waves: Emission” and “It is not
affected by electromagnetic wave from external: Immunity”. The following is describing the contents to meet the
EMC command when configuring the system by using the XGT Panel. This is a summary document for the
request and standard which our company has obtained from EMC but we don't assure that all devices
manufactured according to these contents are not suitable for the below standards. The final manufacturer needs
to finally judge about the fitness method or fitness judgment of EMC command.
12.1.1 CE standard certification
In case of XGT Panel, the EN61000-6-4, EN61000-6-2, EN61000-3-2, and EN61000-3-3 of CE standards were
applied.

Applied Standards Results
1. Emission
Conducted Disturbance EN61000-6-4:2007 / A1 : 2011 C
Radiated Disturbance EN61000-6-4:2007 / A1 : 2011 C
Harmonic Current Emission EN61000-3-2:2014 N/T
Voltage Change, Fluctuations and Flicker EN61000-3-3:2013 N/T
2. Immunity
Electrostatic Discharge EN61000-6-2:2005 / AC : 2005 C
EN61000-4-2:2009
Radio-Frequency Electromagnetic Field EN61000-6-2:2005 / AC : 2005 C
EN61000-4-3:2006 / A1 : 2008 / A2 : 2010
Fast Transient EN61000-6-2:2005 / AC : 2005 C
EN61000-4-4:2004 / A1 : 2010
Radio-Frequency Continuous Conducted EN61000-6-2:2005 / AC : 2005 C
EN61000-4-6:2009
Power-Frequency Magnetic Fields EN61000-6-2:2005 / AC : 2005 N/T
EN61000-4-8:2010
Surges EN61000-6-2:2005 / AC : 2005 C
EN61000-4-5:2006
Voltage Dips and Interruptions EN61000-6-2:2005 / AC : 2005 N/T
EN61000-4-11:2004
C=Comply NC=Not Comply N/T=Not Tested N/A=Not Applicable

 

Chapter 12 EMC Standard Certification

12-2

Directive:
Electromagnetic Compatibility Directive 2004/108/EC

12.1.2 KC standard certification
The XGT Panel acquire the electromagnetic fitness registration (KC specification) certified by wave laboratory
under information-communication part.

A grade device
This device acquires KC for industrial use.
If device is not purchased properly, exchange it to device for home use.

12.2 Requirement for Low Voltage Command Suitability
It is required to get the needed Stability for the device operated at AC50~1000V, DC75~1500V’s power. The
following describes attention about installation and wiring for the suitability when using the XGT Panel. Though
the following data is made by requirement of regulation and standard, we don’t guarantee that all devices are
suitable for the above command. The method to be suitable for the EMC command and judgment of suitability
should be finally made by device manufacturer himself.
12.2.1 Standard certification for XGT Panel
XGT Panel is according to the EN61131-2:2007 (stability of device used in the measure, control laboratory).
12.2.2 Selection of XGT Panel
(1) eXP20-TTA/DC, eXP40-TTe/DC, eXP40-TTA/DC, eXP60-TTA/DC
The I/O module under DC12V exceeds the range of low voltage command target.

Appendix 1 Troubleshooting

App1-1
Appendix 1 Troubleshooting
1. Type of Problem
It classifies problems from XGT Panel including an indicated figure, indication of the object, and problems
appeared when downloading. Refer to the following chart.

Classification of
problem
Description
Problem when starting Malfunction when starting.
Please refer to the 2. Problem when starting.
Problem after the
monitor on
In case that there is no reaction when touching.
Please refer to the 3. Problem after the Monitor on.
Display problem of
figure and object.
In case that the figure or object is different from when editing.
Please refer to the 4. Indication problem of figure and object.
Communication problem In case that communication is not executed properly.
Please refer to the 5. Communication problem.
USB Removal of
Memory Card
In case that USB device is not working for a while when USB memory is removed.
Please refer to the 6. USB Removal of Memory Card
Error message
when executing program
In case that an error message occurs when operating the XGT Panel.
Please refer to the 7. Error message when executing program.

 

Appendix 1 Troubleshooting

App1-2
2. Problem when Starting
Why does black screen show up when turning on the device?
Phenomenon: When turning on the device, black screen shows up and the booting is impossible.
< Cause >
(1) Because the device is not set as a booting mode.
(2) Black screen may appear because of malfunction of backlight.
<Solution>
(1) Because the device is not set as a booting mode, the above problem can occur.
Check whether No. 5 switch at DIP switch in the back of the device is in B direction or not.
B direction is a booting mode.
When is the color of LED changed?
Please check the followings.

Display color Contents
BLUE Power is supplied to XGT Panel

When applying the option, ‘Go to Screen after boot up’, it displays “Failed to load image files” as the
monitoring has not been started.
Phenomenon: After storing images in the USB storage device and then selecting the option “Go to Screen
after boot up” in the start menu, in case when re-permitting the power of the equipment, the message like
“Failed to load image files” is displayed and the monitoring is not started.
<Cause>
(1) In case when it is connected with the USB storage device, the recognition of the USB is delayed.
<Solution>
(1) In case when the recognition speed is delayed due to the characteristics of the USB storage device,
remove the USB storage device and then reinstall it.

Appendix 1 Troubleshooting

App1-3
When the power is re-permitted, the USB storage device (or USB mouse) is not recognized.
Phenomenon: When the USB storage device was initially installed, it was normally recognized. However, it is
not recognized after the power is re-permitted.
<Causes>
(1) Due to the option of the ‘Reset USB Power’ of the equipment, there could problems in the recognition
process.
(2) Depending on the USB storage device, it may not be smoothly recognized.
<Solution>
(1) If the power initialization option(“Reset USB Power”) of the equipment is selected, cancel the selection
and then permit the power again. The “Reset USB Power” option is an additional function to improve
the initialization of the storage device with slow recognition speed or low recognition ratio. Depending
on the characteristics of the storage device, however, the power initialization can be an obstacle to the
initialization work. Thus, depending on Phenomenon, select what has higher recognition ratio by
properly using the power initialization option.
(2) Depending on the characteristics of the storage device, it may not be recognized. Use another USB
storage device showing higher recognition ratio.

Appendix 1 Troubleshooting

App1-4
3. Problem after the Monitor on
When touching the screen it reacts in a different area or it may not react at all?
Phenomenon: When touching the screen it reacts in a different area or it may not react at all.
< Cause >
(1)Touch’s Calibration setting is not proper.
(2) Touch panel may be a break down.
<Solution>
(1) Redo Calibration setting about touch. Refer to the [Device manual Ch.4.1 Touch Calibration].
(2) It you can’t go to setting menu, connect mouse to USB port and use mouse.
Buzzer does not sound.
Phenomenon: When pressing buzzer, buzzer does not sound.
< Cause >
(1) When that the switch operates but the buzzer doesn’t sound, the buzzer is set as no sound.
(2) If the switch doesn’t work too, it seems that some error occurs in the touch function.
<Solution>
(1) Redo environment setting for buzzer to sound. Refer to the [device manual Ch.4.7 Environment Setting].
(2) After setting to use buzzer, check whether the buzzer sounds or not in the 1)’s setting windows.
Phenomenon: After the system alarm about the lack of system memory occurs, XGT Panel itself closes the
monitoring and then moves to the start menu in unspecific time without user’s operation.
<Causes>
(1) The memory usage could be exceeding 95%.
(2) The memory usage can be a bit increased when floating pop-up windows or moving to several screens
during monitoring. In case when the number of image used for project is a lot, the memory usage can
more easily reach the limit. In this case, XGT Panel closes the monitoring by itself and then takes an
action to secure the memory again.
<Solution>
(1) In case of using vector image instead of raster image, the memory share can be reduced. In the graphic
library of XP-Builder, the image group marked as OOO_R is the raster image group while the image
group marked as OOO_V is the vector image group.
(2) In case when the monitoring is closed down due to the increase of the memory share in spite of the
image change operation, contact the A/S center close by.

Appendix 1 Troubleshooting

App1-5
After continuously adding projects to the screen, and adding/editing objects, the operation speed has
been slowed down.
Phenomenon: After adding projects to the screen and also adding/editing objects, it feels like the operation
speed of XGT Panel gets slowed down.
<Causes>
(1) The amount of image used for projects is big.
(2) In order to increase the screen operation speed, XGT Panel maintains the used images in the memory in
advance. Since the memory resource has limitation, they cannot be maintained in the memory once the
amount of image exceeds a certain limit. Whenever they are needed, thus, they are read from the file
system and then expressed on the screen. This could be the reason why the screen operation speed gets
slowed down.
<Solution>
(1) In case of using vector image instead of raster image, the memory share can be reduced. In the graphic
library of XP-Builder, the image group marked as OOO_R is the raster image group while the image
group marked as OOO_V is the vector image group.
(2) In case when there is no proper vector image, the desired image can be composed by using various
functions of figures (circle, square, straight line and etc.).
(3) Removing unnecessary background screen, the screen is composed by applying the background colors.

Appendix 1 Troubleshooting

App1-6
4. Display Problem of Figure and Object
The shape of object is not shown or the number or character value which has to be shown is not shown.
Phenomenon: The shape of object is not shown or the number or character value which has to be shown is
not shown.
<Cause>
(1) The connection with PLC connected with each project is disconnected or NAK occurs.
<Solution>
(1) When the communication is executed at first, Check the cable connected with PLC is OK or not.
(2) If object where the offset is set is not shown, check whether address range is exceeded or not.
(3) In case that communication is not OK, when communication is abnormal, the following message shows
up in the XGT Panel.

Object type Phenomenon
Bit Switch The switch is expressed but it doesn’t work.
Word Switch The switch is expressed but it doesn’t work.
Change Screen Switch The switch is expressed but it doesn’t work.
Special Switch The switch is expressed but it doesn’t work.
Multi Switch The switch is expressed but it doesn’t work.
Bit Lamp Image is not shown.
Word Lamp Image is not shown.
N-State Lamp Image is not shown.
Clock Present time is shown.
Bit Message Message is not shown. When designating the background image, image is shown
as it is.
Word Message Message is not shown. When designating the background image, image is shown
as it is.
Numeric Display The value is not shown. When designating the background image, image is shown
as it is.
Numeric input The value is not shown. When designating the background image, image is shown
as it is.
Text Display Character string is not shown. When designating the background image, image is
shown as it is.
Text Input Character string is not shown. When designating the background image, image is
shown as it is.
Bit Window The window screen set in the object is not shown. But if communication is set with
other object in the same window screen, it can be shown by that object.
Word Window The window screen set in the object is not shown. But if communication is set with
other object in the same window screen, it can be shown by that object.
Bit Part The part screen set in the object is not shown. But if communication is set with
other object in the same part screen, it can be shown by that object.
Word Part The part screen set in the object is not shown.

 

Appendix 1 Troubleshooting

App1-7

Object type Phenomenon
But if communication is set with other object in the same part screen, it can be
shown by that object.
Animation Animation is not shown.
Bar Graph Graph is not shown. When designating the background image, image is shown as
it is.
Pie Graph Graph is not shown. When designating the background image, image is shown as
it is.
Meter Graph Graph is not shown. When designating the background image, image is shown as
it is.
Closed Graph Graph is not shown. When designating the background image, image is shown as
it is.
Trend Graph X, Y axis is shown normally but trend axis is not normally shown.
When designating the background image, image is shown as it is.
History Alarm Viewer Change doesn’t occur. When communication is abnormal, alarm occurs because it
can’t know the status of alarm target device. But previous alarm data shows up as
it is.
Data list Value is not shown. Lattice of viewing data list of object is shown as it is.
Logging Viewer Change doesn’t occur. When communication is normal, the recorded log data is
shown normally. But, log data is shown as # when communication is abnormal.
Navigator Change doesn’t occur. Because it shows the group of alarm already developed,
though communication is abnormal, if it has alarm data already developed, it
shows the name of group where each alarm is included.

The number indication object value is shown as # or ~.
Phenomenon: The number indication object value is shown as # or ~.
(Same phenomenon occurs at the number input device, viewing data list, and viewing logging)
<Cause>
(1) This happens when digit is not correct or type is not BCD.
<Solution>
(1) When the number to be expressed exceeds the number set in the object, # is expressed. In case of this,
set the digit largely and after download again, execute program again.
(2) When the numeric display object is expressed as BCD type, the data whose type is not BCD is
expressed as ~. In case of this, adjust device value as BCD type.
(3) This phenomenon occurs at the data list object, numeric input, numeric display device, and logging
viewer.

Appendix 1 Troubleshooting

App1-8
After switching the screen, the previous screen remains for a few minute.
Phenomenon: After switching the screen, when there is no background or image in the part or number
indication device, the previous screen remains for a few minute because of change of part.
< Cause >
(1) After switching the screen, when connection is set up multiply or communication time-out occurs, the
screen of previous part remains in some object.
<Solution>
(1) It is normal status. In case that multiple connection or communication is not good, when switching the
screen, the remains of previous screen can occur during the time-out hour.
The folded object doesn’t sequentially show up.
Phenomenon: The number under the data list shows up above data list.
< Cause >
(1) The device value is expressed at the top of object screen.
<Solution>
(1) It is normal status. The folded window or part object is not included in screen, regardless of sequence of
drawing, the object changed recently is expressed at top of screen. So if possible, do not fold the object
in screen.
The object always shows up above the figure.
Phenomenon: I downloaded the figure above the object in XP-Builder, but the object always shows up above
the figure.
< Cause >
(1) In XGT Panel, The object always shows up above the figure.
<Solution>
(1) It is normal status. The object always shows up above figure in the XGT Panel.

Appendix 1 Troubleshooting

App1-9
5. Communication Problem
It seems that communication does not work.
Phenomenon: On the screen where the object is not many, communication works but when you move the
screen where the object is many, timeout occurs.
< Cause >
(1) In the device setting, the communication time-out is set to be too short.
<Solution>
(1) It occurs because timeout is set much smaller than sum of request time of communication data and
response time from PLC. In the device setting at the XP-Builder, after setting communication time out to
be big, download program and execute again.
It seems that communication doesn’t work.
Phenomenon: Communication doesn’t work.
< Cause >
(1) Communication setting or cable may be not normal.
<Solution>
(1) In case of RS-232C, check whether connection setting is normal or not in XP-Builder.
(2) In case of RS-422/485, check whether station and communication connection setting is normal or not.
(3) If 1), 2) is normal, do diagnosis about PLC-RS232C, PLC-RS485/422 at the Serial diagnosis screen of
device menu. Refer to the [Device manual ch.5.6 Serial Communication Diagnosis]
(4) If 3) is normal, check whether connection cable has error or not.
(5) In case of Ethernet, check the port and IP setting about relative PLC.
► Before trial operation of the product, be sure to check if a normal communication is available
between XGT Panel and the subject device of control
Caution

Appendix 1 Troubleshooting

App1-10
6. USB Removal of Memory Card
When removing the USB memory equipment, device is stopped for some times.
Phenomenon: This happens when doing data backup including logging, recipe.
< Cause >
(1) This happens because memory card is removed when doing data backup.
<Solution>
(1) If possible, when monitoring XGT Panel, do not remove the memory card and after going out to the
waiting screen, execute the removing.
(2) Inescapably you have to remove it during the operation, remove when backup does not occur. If the
above phenomenon occurs, it works normally after about 10 seconds.
(3) In case of USB memory, please remove it when the LED of USB external memory is not flickering.
After the repeated attachment/detachment of the USB storage device, it is not recognized.
Phenomenon: It can happen when the attachment/detachment of the USB device is repeated for a short
period of time.
<Cause>
(1) When the USB device is recognized or removed, it takes a certain period of time(maximum a few
seconds) to recognize it. When the storage device is quickly installed/removed, however, it cannot be
normally recognized.
<Solution>
(1) It is recognized again after waiting for about a minute. Install it again after waiting for more than a minute.
(2) When removing/reinstalling the USB device, reinstall it after waiting for around 2-3 seconds.
Caution
► If you force to remove the data during the storage of data in the external memory, file may not
be stored in a normal condition or external memory may suffer from damage.

Appendix 1 Troubleshooting

App1-11
7. Error Message during Execution of Program
In case that problems occur during execution of XGT Panel including the start of device, diagnosis of device and
environment setting, project download, monitoring of control device, and error messages occur as type of box. At
this time the message indicates the code made by 4 digit number. The front 2 number indicate code of object
and work, the rear 2 number is message number. In case that the present error message is indicated as [0101],
an error message occurs when doing diagnosis about the status of NVRAM. When an error message occurs,
refer to the row’s number and sequence and find the category of reason and measure.

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
Device
diagnosis
0x01 0x01 XGT
Panel
NVRAM Data
Access ... FAILED!
Failed to check whether backup
memory is normal or not. If this
symptom is repeated, contact the near
Customer Service Center.
0x02 XGT
Panel
BATTERY STATUS ...
NOT GOOD!
Backup data is not valid. If this
symptom is repeated when turning
power off and on, remove XGT Panel’s
power and exchange the battery.
0x03 XGT
Panel
Write Operation
FAILURE!
The built-in Flash disk has an error.
Contact the near Customer Service
Center.
0x04 XGT
Panel
Read Disk Information
Error!
The built-in Flash disk has an error.
Contact the near Customer Service
Center.
0x05 XGT
Panel
Write Operation
FAILURE!
Check that CF card is empty, and equip
CF card and test again. If same
symptom is repeated, CF card or CF
card slot of XGT Panel may have a
problem.
0x06 XGT
Panel
Read Disk Information
Error!
Check that CF card is empty, and equip
CF card and test again. If same
symptom is repeated, CF card or CF
card slot of XGT Panel may have a
problem.
Device
setting
0x02 0x01 XGT
Panel
Invalid timeout value. You inputted the wrong time which is
not within backlight setting time range.
Input the effective time.
0x02 XGT
Panel
Not found XGT Panel
configuration file.
There is no setting information data of
XGT Panel. If this symptom is repeated
when turning power off and on, contact
the near Customer Service Center.
0x03 XGT
Panel
Please enter an
integer between 0 and
255.
When setting IP, the values within
0~255 are effective. Input the value
within the above range.

 

Appendix 1 Troubleshooting

App1-12

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
Viewing
device
information
0x03 0x01 XGT
Panel
No project in XGT
Panel.
Now, there is no downloaded project so
you can’t see connection information.
Download the project from XP-Builder.
XGT Panel
Update
0x04 0x01 Panel XGT Failed to Start engine. Please update engine
again.
Because of update error or Flash disk
error, program can’t be executed. If you
can update, redo the above procedure.
If you can’t, contact the near Customer
Service Center.
Switch h05 h01 XGT
Panel
Invalid password. There is password in the each object.
When editing the project downloaded in
the present device, input the
designated password at the project
property information.
Number
indication
device/
Number
input device
0x06 h01 XGT
Panel
Can't write Data. Because of communication error, the
value can’t be inputted. Check the
communication status and input again.
h02 XGT
Panel
No input Data. You tried to input with no value. Input the value
0x03 XGT
Panel
Exceeded the max
length.
You exceed the maximum length to
input.
0x04 XGT
Panel
Exceeded the
minimum Value.
You exceed the maximum value to
input.
0x05 XGT
Panel
Exceeded the
maximum Value.
You exceed the minimum value to
input.
0x06 XGT
Panel
Invalid at Input Case. When you input the value, input can’t
be done because of wrong input. Check
the input condition of each object in the
Builder and input again.
Lamp 0x07 None
Character
indication
device/
Character
input device
0x08 None
Message 0x09 None
Clock 0x0A None
Animation 0x0B None
Graph 0x0C None
Window 0x0D None
Part 0x0E None
History
alarm
0x0F None
Flow alarm 0x20 None
System
alarm
0x21 None

 

Appendix 1 Troubleshooting

App1-13

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
Scheduler
related
0x22 None
Recipe
related
0x23 None
Logging
related
0x24 None
Data list 0x25 None
Project
download
0x26 0x00 XGT
Panel
Abnormal send
payload. Please
download project
again.
Communication status is abnormal.
Check the connection of
communication cable.
0x01 XP
Builder
There's not Password
File.
This message shows up when making
it newly because there is no password
setting file in the device. When making
it newly, it is initialized with no
password.
0x02 XP
Builder
Failed to Create
Password File.
It make new password setting file when
there is no password setting file. But
downloading is stopped when it fails to
make this file because of device error.
If this problem is repeated, Contact the
near Customer Service Center.
0x03 XP
Builder
Invalid Backup Media. Communication status is abnormal.
Route information is not correct to save
project data. If this problem is repeated,
Contact the near Customer Service
Center.
0x04 XP
Builder
Failed to Create
version File.
In case that the version information file
doesn’t exist in the device, that file is
made newly. In case that the device
has error and fails to make that file,
download is stopped. If this problem is
repeated, Contact the near Customer
Service Center.
0x05 XP
Builder
File Size Error. There is version information file. In
case that because of error of device, it
fails to read version information,
because the device doesn’t know
version, download is stopped. If this
problem is repeated, Contact the near
Customer Service Center.

 

Appendix 1 Troubleshooting

App1-14

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
0x06 XP
Builder
Failed to get Project
ID.
In case of not reading file where project
property is included, download is
stopped. If this problem is repeated,
Contact the near Customer Service
Center.
0x07 XP
Builder
Failed to read history
alarm data.
In case of not reading information about
alarm history because of error of
NVRAM, download is stopped. If this
problem is repeated, Contact the near
Customer Service Center.
0x08 XP
Builder
Failed to read CF
Card information.
Project is set to store data at CF card
equipped at device. By the way, now it
can’t read information about CF card.
Check the installation status of CF card
and if it is normal, check the CF card. If
this problem is repeated, contact
Customer Service Center.
Project
download
0x26 0x09 XP
Builder
Failed to read USB
information.
Project is set to store data at USB
storage device equipped at device. By
the way, now it can’t read information
about USB storage device. Check the
installation status of USB storage
device and if it is normal, check USB
storage device. If this problem is
repeated, contact Customer Service
Center.
0x0A XP
Builder
Failed to read Flash
memory information.
In case that it can’t know information
about memory status, download is
stopped. If this problem is repeated,
contact Customer Service Center.
0x0B XP
Builder
Failed to clear Temp
Directory.
In case that because of error of Flash
Disk, it can’t delete the directory made
temporally for download because of
error of Flash Disk, download is
stopped. If this problem is repeated,
contact Customer Service Center.
0x0C XGT
Panel
Failed to delete Font
File. Please reboot
XGT Panel.
In case that it fail to delete the font file
of previous project because of error of
XGT Panel, download is stopped. If this
problem is repeated, contact Customer
Service Center.
0x0D XGT
Panel
Failed to delete Image
File. Please reboot
XGT Panel.
In case that it fail to delete the image
file of previous project because of error
of XGT Panel, download is stopped. If
this problem is repeated, contact

 

Appendix 1 Troubleshooting

App1-15

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
Customer Service Center.
0x0E XGT
Panel
Failed to delete Sound
File. Please reboot
XGT Panel.
In case that it fail to delete the sound
file of previous project because of error
of XGT Panel, download is stopped. If
this problem is repeated, contact
Customer Service Center.
0x0F XGT
Panel
There's no
downloaded project. It
needs to download
whole project
It can’t download part or fixed part in
case there is no downloaded project. In
case of this, download again. If this
problem is repeated, contact Customer
Service Center.
0x10 XP
Builder
Backup path is invalid.
Please check the path
that project is
downloaded.
When user change the storage location
of project data including image and
font, if there is not respective routine, it
make newly. By the way, download is
stopped in case it fails to make newly.
When it is designated as CF card, it
can occur in case CF card is not
installed. If this problem is repeated
and not referred in the above, contact
Customer Service Center.
0x11 XGT
Panel
Failed to delete
previous project
archive. Please reboot
XGT Panel.
The project backup file downloaded
already can be deleted because of
error of XGT Panel. Reboot XGT Panel.
If this problem is repeated, contact
Customer Service Center.
Project
download
0x26 0x12 XGT
Panel
Failed to delete past
project data files.
Please download
project again.
When downloading, the log data area in
the NV-RAM is initialized in case of
selecting previous project’s the monitor
data deletion option. By the way, in
case of failing this, downloading is
stopped. If this problem is repeated,
contact Customer Service Center.
0x15 XGT
Panel
Failed to initialize
LOGGING area in NV
RAM. Please
download project
again.
When downloading, the log data area in
the NV-RAM is initialized in case of
selecting previous project’s the monitor
data deletion option. By the way, in
case of failing this, downloading is
stopped. If this problem is repeated,
contact Customer Service Center.

 

Appendix 1 Troubleshooting

App1-16

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
0x16 XGT
Panel
Failed to initialize
RECIPE area in NV
RAM. Please
download project
again.
When downloading, the alarm history in
the NV-RAM is initialized in case of
selecting the previous project’s monitor
data deletion option. By the way, in
case of failing this, downloading is
stopped. If this problem is repeated,
contact Customer Service Center.
0x17 XGT
Panel
Failed to initialize
ALARM area in NV
RAM. Please
download project
again.
The downloaded font file is moved into
original storage location but when this
fails, downloading is stopped. If this
symptom is repeated, contact
Customer Service Center.
0x18 XGT
Panel
Failed to install font
files. Please download
project again.
The project data is divided into several
files according to the contents but when
this fails, downloading is stopped. If this
symptom is repeated, contact
Customer Service Center.
0x19 XGT
Panel
Failed to unmarshall
download file. Please
download project
again.
The data divided according to the
contents is moved to the original
storage location but when this fails,
downloading is stopped. If this
symptom is repeated, contact
Customer Service Center.
0x1A XGT
Panel
Failed to install new
project data files.
Please download
project again.
The downloaded project is not installed
normally because of error of the Flash
Disk. Download the project again. If this
symptom is repeated, contact
Customer Service Center.
0x1B XGT
Panel
Failed to merge data
files. Please download
project again.
The downloaded project zip file is
moved to the original storage location
but when it fails, downloading is
stopped. If this symptom is repeated,
contact Customer Service Center.
0x1C XGT
Panel
Failed to save new
project archive. Please
download project
again.
There is a program to reboot engine
program after downloading in the
device but when it fails, this message
shows up. But because the
downloading is completed if you reboot
engine directly, it works normally. The
program name to reboot is startup.exe
and it can be installed by engine
upgrade function.

 

Appendix 1 Troubleshooting

App1-17

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
Project
download
0x26 0x1D XGT
Panel
Failed to XGP Panel
startup program.
Please update XGT
Panel Software.
It can’t find software to reboot XGT
Panel.
Update the XGT Panel.
0x1E XGT
Panel
Project data is not
downloaded. Please
download project
again.
The project data was not downloaded
normally because of communication
error. Check the connection status of
communication cable and If this
symptom is repeated, contact
Customer Service Center.
0x1F XGT
Panel/
XP
Builder
Failed to read Version
information file. Please
download project
again.
There is version information file but
when it can’t read file normally because
of the device error, downloading is
stopped because it doesn’t know
version. If this symptom is repeated,
contact Custom Service Center
Project
download
from USB
storage
device
0x27 0x51 XGT
Panel
Cannot find project
data in USB Storage
There is no USB or device status of
USB is not good or project is not saved
properly.
0x52 XGT
Panel
Project information file
is not in USB Storage.
The project is not saved normally in the
USB.
Check whether there is XP_Project
folder and [project name].inf in the USB
or not.
0x53 XGT
Panel
Failed to read project
information file.
It can’t read project information file
because the project is not saved in the
USB normally. Save the project again
from XP-Builder to the USB.
0x54 XGT
Panel
Device type is not
matched.
The connected device type is not same
as the device type set in the project in
the USB. In case of this, project can’t
be downloaded into the device. Edit the
project again or download according to
the connected device.
0x55 XGT
Panel
Cannot read user
password.
Information about the password can’t
be red because of the device error. If
this symptom is repeated, contact
Customer Service Center.
0x56 XGT
Panel
Password is not
matched.
When saving the project, the password
inputted by user is not same as present
connection password. Input correct
password and save the project.

 

Appendix 1 Troubleshooting

App1-18

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
Project
download
from USB
storage
device
0x27 0x57 XGT
Panel
Cannot read XGT
Panel software
version.
There is version information file but
when it can’t read file normally because
of the device error, downloading is
stopped because it doesn’t know
version. If this symptom is repeated,
contact Customer Service Center.
0x58 XGT
Panel
XGT Panel software is
old version. Please
update XGT Panel.
The version of XP-Builder where
project is saved is not compatible with
present XGT Panel. Update the XGT
Panel.
0x58 XGT
Panel
XP-Builder is old
version. Please
update XP-Builder.
The version of XP-Builder where
project is saved is not compatible with
present XGT Panel. Update the XGT
Panel.
0x59 XGT
Panel
Cannot read download
data format version.
There is storage structure version
information file. But when it can’t read
this file because of the device error,
downloading is stopped because it
doesn’t know the version. If this
symptom is repeated, contact
Customer Service Center.
0x5A XGT
Panel
Download data format
version is not
matched. Please
update XGT Panel.
Data storage type is not correct.
Update XGT Panel.
0x5A XGT
Panel
Download data format
version is not
matched. Please
update XP-Builder.
Data storage type is not correct.
Update the XP-Builder.
0x5B XGT
Panel
Data file path is
invalid.
There is no project data file at
designated location. Check the
connection status of USB and if there is
no error, save the project to USB again.
0x5C XGT
Panel
Download file name
length is invalid.
The name of project data file is not
saved correctly. Save the project at the
USB again. If this symptom is repeated,
contact Customer Service Center.
0x5D XGT
Panel
Cannot find download
file.
The project data file can’t be found.
Save the project data file at the USB
again. When this symptom is repeated,
check the USB. If there is no error,
contact Customer Service Center.

 

Appendix 1 Troubleshooting

App1-19

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
0x5E XGT
Panel
Download file size is
invalid.
The project data file is not saved
correctly. Save the project data file at
the USB again. When this symptom is
repeated, check the USB. If there is no
error, contact Customer Service
Center.
Project
download
from USB
storage
device
0x27 0x5F XGT
Panel
Cannot find project
backup file.
The project backup file which should be
downloaded is not downloaded
because of communication error.
Download again.
0x60 XGT
Panel
Project backup file
size is invalid.
The project backup file is saved
incorrectly. Save the project at the USB
storage equipment again. When this
symptom is repeated, check the USB
storage equipment and if the USB is
normal, contact Customer Service
Center.
0x61 XGT
Panel
Font file name length
is invalid.
The font file’s name is saved
incorrectly. Save the project in the USB
again. If this symptom is repeated,
contact Customer Service Center.
0x62 XGT
Panel
Font file is not
downloaded.
The font file which is needed for project
is not saved in the USB storage
equipment. Save the project in the
USB. If this symptom is repeated,
contact Customer Service Center.
0x63 XGT
Panel
Font file size is invalid. The font file is not saved correctly.
Save the project at the USB. Save the
project at the USB. If this symptom is
repeated, check the USB and if the
USB is normal, contact Customer
Service Center.
0x64 XGT
Panel
Cannot unmarshall
download file.
The data can’t be analyzed because
the project data file is not saved
correctly. Save the project at the USB
again. If this symptom is repeated,
check the USB and if the USB is
normal, contact Customer Service
Center.
0x65 XGT
Panel
Cannot delete
previous project data.
The data of the project can’t be deleted
because of device error. If this
symptom is repeated, check the USB
and if the USB is normal, contact
Customer Service Center.

 

Appendix 1 Troubleshooting

App1-20

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
0x66 XGT
Panel
Cannot move new font
files.
Downloaded font file is moved to the
original storage location. But when it
fails, the downloading is stopped. If this
symptom is repeated, contact
Customer Service Center.
0x67 XGT
Panel
Cannot move new
project data files.
The project data classified according to
the content is moved to the original
storage location. But when it fails, the
downloading is stopped. If this
symptom is repeated, contact
Customer Service Center.
0x68 XGT
Panel
Cannot move project
backup file.
The downloaded project zip data is
moved to the original storage location.
But when it fails, the downloading is
stopped. If this symptom is repeated,
contact Customer Service Center.
XGT Panel
booting
0x28 0x01 XGT
Panel
Previous instance is
not terminated.
XGT Panel software was already
started. Reboot the device. If this
symptom is repeated, contact
Customer Service Center.
0x02 XGT
Panel
Start Server Fail.
Restart XGT Panel
The XGT Panel software can’t initialize
the communication status normally.
Check the communication status again.
If this symptom is repeated when
communication is normal, contact
Customer Service Center.
0x03 XGT
Panel
Failed to Start Echo
Server.
The XGT Panel software can’t initialize
the communication status normally.
Check the communication status again.
If this symptom is repeated when
communication is normal, contact
Customer Service Center.
0x04 XGT
Panel
Failed to accept
connection.
The XGT Panel software can’t initialize
the communication with the XP-Builder
normally. Check the communication
status again. If this symptom is
repeated when communication is
normal, contact Customer Service
Center.

 

Appendix 1 Troubleshooting

App1-21

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
0x05 XGT
Panel
Failed to rename
UpdateNew.exe
In the present XGT Panel the new
updated XGT Panel software’s name
can not be changed.
After rebooting the XGT Panel, update
again. When rebooting, if you can’t start
engine, delete
FlashDiskLSISProductUpdateNew.e
xe in the XGT Panel. Then if you touch
Update.exe and execute the XGT
Panel, it can be update mode. Try
update again. If this symptom is
repeated, contact Customer Service
Center
0x06 XGT
Panel
Failed to Delete
Update.exe.
The new module is downloaded by the
XGT Panel update but the previous
module is not deleted. Reboot the
device. If the XGT Panel software is not
started normally, touch
FlashDiskLSISProductUpdate.exe in
the XGT Panel. At this time, if XGT is
set as update mode, update again. If
this symptom is repeated, contact
Customer Service Center.
Communica
tion
between
other XP
Builder
XGT Panel
0x29 0x30 XGT
Panel
Failed to modify
password file.
The device connection password can’t
be modified because of error of Flash
Disk of XGT Panel. Reboot the device.
If this symptom is repeated, contact
Customer Service Center.
0x31 XGT
Panel
Password-related
command
transmission payload
error
It failed to set and modify password
because of communication status error.
If this symptom is repeated, contact
Customer Service Center.
0x32 XGT
Panel
There is no XGT
Panel connection
setting file.
The connection setting file of XGT
Panel can’t be found.
0x33 XGT
Panel
Modified content can’t
be saved in the XGT
Panel connection
setting file.
The modified information can’t be
saved at the connection setting file of
XGT Panel. If this symptom is
repeated, contact Customer Service
Center.
0x34 XGT
Panel
Failed to set the time The XGT Panel’s time can’t be set. If
this symptom is repeated, contact
Customer Service Center.

 

Appendix 1 Troubleshooting

App1-22

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
XGT panel
S/W update
0x30 0x21 XGT
Panel/
XP
Builder
Failed to Create
Initialized Module
Version File.
Because the each module version
information can’t be read because of
XGT Panel’s error, it failed to initialize.
If this symptom is repeated, contact
Customer Service Center.
0x22 XGT
Panel/
XP
Builder
Module version file
size is invalid.
The each module version information
can’t be read because of XGT Panel’s
error. If this symptom is repeated,
contact Customer Service Center.
0x23 XGT
Panel/
XP
Builder
Can't Read module
version file.
The each module version information
can’t be read because of XGT Panel’s
error. If this symptom is repeated,
contact Customer Service Center.
0x24 XP
Builder
There's no file to
download.
The version information list to update is
empty. Check the module folder newly
designated at XP
Builder and if there is no error,
download XGT Panel module and try
update again. If this symptom is
repeated, contact Customer Service
Center.
0x25 XP
Builder
Downloaded file is not
Module to download.
The wrong file which is not in the new
module list of XGT Panel is
downloaded. Try update of XGT Panel
again. If this symptom is repeated,
contact Customer Service Center.
XGT panel
S/W update
0x30 0x26 XGT
Panel
Not enough space in
flash memory.
The space to copy new module in XGT
Panel is not enough. After deleting the
unnecessary file or backing up the
previous file to the movable storage
equipment, try update again. If this
symptom is repeated after deleting,
contact Customer Service Center.
0x27 XGT
Panel
Failed to Copy module
~.dll
The new module is not installed
because of XGT Panel’s error. After
rebooting the device, touch
FlashDiskLSISProductUpdate.exe
and set the device as update mode.
Then update again. If this symptom is
repeated, contact Customer Service
Center.

 

Appendix 1 Troubleshooting

App1-23

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
0x28 XGT
Panel
Failed to Start Engine.
Please update engine
again.
To reboot the engine is not available
because of wrong file which is
developed by downloading wrong
module or communication error.
Touch
FlashDiskLSISProductUpdate.exe
and set the device as update mode.
Then update again. If this symptom is
repeated, contact Customer Service
Center.
0x2A XGT
Panel
Failed to write Data to
Module version File.
It is failed to record the version
information during update of XGT
Panel. If this symptom is repeated,
contact Customer Service Center.
0x2B XGT
Panel
There's no
downloaded file.
To reboot the engine is not available
because of wrong file which is
developed by downloading wrong
module or communication error.
Touch
FlashDiskLSISProductUpdate.exe
and set the device as update mode.
Then update again. If this symptom is
repeated, contact Customer Service
Center.
0x2C XGT
Panel
(improper
communication
command)
Current state is not
authorized.
To reboot the engine is not available
because of wrong file which is
developed by downloading wrong
module or communication error.
Touch
FlashDiskLSISProductUpdate.exe
and set the device as update mode.
Then update again. If this symptom is
repeated, contact Customer Service
Center.
XGT panel
S/W update
0x30 0x2D Panel XGT (improper
communication
command)
A module to download
is not listed up yet.
To reboot the engine is not available
because of wrong file which is
developed by downloading wrong
module or communication error.
Touch
FlashDiskLSISProductUpdate.exe
and set the device as update mode.
Then update again. If this symptom is
repeated, contact Customer Service
Center.

 

Appendix 1 Troubleshooting

App1-24

Object Error code Occurrenc
e location
Error message Reason and measure
Type Address
0x2E XGT
Panel
Failed to Initialize
Update program.
XGT can’t be set as update mode
because of XGT Panel error. After
downloading new XGT Panel module
through homepage, etc., copy
UpdateNew.exe file among new
module to the
FlashDiskLSISProduct directory of
XGT Panel through the movable
storage equipment. Then reboot the
XGT Panel and go update mode and
update again. If this symptom is
repeated, contact Customer Service
Center.

 

Appendix 2. Dimension

App2-1
Appendix 2. Dimension (Unit: mm)
(1) eXP20-TTA/DC

Appendix 2. Dimension

App2-2
(2) eXP40-TTA/DC, eXP40-TTE/DC

Appendix 2. Dimension

App2-3
(3) eXP60-TTA/DC, eXP60-TTE/DC

Appendix 3 Warranty and Environmental Policy

App3-1
Appendix 3 Warranty and Environmental Policy
Warranty
1. Warranty Period
The product you purchased will be guaranteed for 18 months from the date of manufacturing.
2. Scope of Warranty
Any trouble or defect occurring for the above-mentioned period will be partially replaced or repaired.
However, please note the following cases will be excluded from the scope of warranty.
(1) Any trouble attributable to unreasonable condition, environment or handling otherwise specified in the
manual
(2) Any trouble attributable to others’ products
(3) If the product is modified or repaired in any other place not designated by the company
(4) Due to unintended purposes
(5) Owing to the reasons unexpected at the level of the contemporary science and technology when
delivered
(6) Not attributable to the company; for instance, natural disasters or fire
3. Since the above warranty is limited to HMI unit only, make sure to use the product considering the safety for
system configuration or applications.
Environmental Policy
LS Industrial Systems Co., Ltd supports and observes the environmental policy as below.
LS Industrial Systems considers the
environmental preservation as the
preferential management subject and
every staff of LS Industrial Systems use
the reasonable endeavors for the
pleasurably environmental preservation of
the earth.
LS Industrial HMI is designed to protect
the environment.
For the disposal, separate aluminum,
iron and synthetic resin (cover) from the
product as they are reusable.
Environmental About Disposal
LS Industrial Systems constantly endeavors to improve its product so that
information in this manual is subject to change without notice.
LSIS Co., Ltd 2015 All Rights Reserved.
10310001449
2016. 07
LS values every single customers.
Quality and service come first at LSIS.
Always at your service, standing for our customers.
www.lsis.com
HEAD OFFICE
LS tower, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 1026-6,
Korea
http://www.lsis.com
Tel : (82-2)2034-4870/Fax : 82-2-2034-4648 e-mail : cshwang@lsis.com
LSIS Tokyo Office _ Tokyo, Japan
Address: 16FL. Higashi-Kan. Akasaka Twin Tower 17-22,
Akasaka.Monato-ku Tokyo 107-8470. Japan
Tel : 81-3-3582-9128/Fax : 81-3-3582-2667
e-mail : jschuna@lsis.com
LSIS(ME) FZE _ Dubai, U.A.E.
Address : Jafza View Tower Lob 19, Room 205 Along Sheikh Zayed
Road Jebel Aali Free Zone Dubai, United Arab Emirates
Tel : 971-4-886-5360/Fax : 971-4-886-5361
e-mail : jungyongl@lsis.com
LSIS Shanghai Office _ Shanghai, China
Address : Room E-G. 12FL Hiamin Empire Plaza. No.726. West.
Yan'an Road Shanghai 200050. P.R. China
e-mail : liyong@lsis.com.cn
Tel : 86-21-5237-9977(609)/Fax : 89-21-5237-7189
LSIS Beijing Office _ Beijing, China
Address : B-Tower 17FL. Beijing Global Trade Center B/D. No. 36.
East BeisanHuan-Road. DongCheng-District. Beijing 100013. P.R. China
Tel : 86-10-5825-6027(666)/Fax : 86-10-5825-6028
e-mail : xunmj@lsis.com.cn
LSIS Guangzhou Office _ Guangzhou, China
Address : Room 1403.14FL. New Poly Tower.
2 Zhongshan Liu Road.Guangzhou.P.R China
Tel : 86-20-8328-6754/Fax : 86-20-8326-6287
e-mail : chenxs@lsis.com.cn
LSIS Chengdu Office _ Chengdu, China
Address : 12FL. Guodong Buiding. No.52 Jindun
Road Chengdu.610041. P.R. China
Tel : 86-28-8612-9151(9226)/Fax : 86-28-8612-9236
e-mail : comysb@lsis.com
LSIS Qingdao Office _ Qingdao, China
Address : YinHe Bldg. 402 Room No. 2P Shandong Road,
Qingdao-City,Shandong-province 266071, P.R. China
Tel : 86-532-8501-6068/Fax : 86-532-8501-6057
e-mail : wangzy@lsis.com.cn
LSIS Europe B.V.
Address : 1st. Floor, Tupolevlaan 48, 1119NZ, Schiphol-Rijk, The Netherlands
Tel : +31 (0)20 654 1420/Fax : +31 (0)20 654 1429
e-mail : junshickp@lsis.com
LSIS(Wuxi) Co., Ltd _ Wuxi, China
Address : 102-A. National High & New Tech Industrial Development Area.
Wuxi. Jiangsu. 214028. P.R. China
Tel : 86-510-8534-6666/Fax : 86-510-8534-4078
e-mail : caidx@lsis.com.cn