- Version 2016.12
- Download 1422
- Tamanho do Arquivo 944.86 KB
- File Count 1
- Data de Criação 26 de março de 2020
- Ultima Atualização 26 de março de 2020
Leaflet H100
H100 BYPASS
HVAC/PUMP Application
HVAC applications can be optimized
with the new H100 Bypass.
The Bypass series offers security
with no downtime and energy savings
using the H100 VFD.
Capacity
200V Class 5.5~18.5kW (7.5~25HP)
400V Class 5.5~55kW (7.5~75HP)
Features
3 Contactor Bypass
HAND/OFF/AUTO selectable
Compact Size
Built-in AC/DC Reactor (Option)
Easy Wiring and Installation
Built-in Operation Indicator
Auto Bypass Function
Motor OL Trip Detection
Easy Maintenance
Built-in Bacnet, Metasys and Modbus Protocols
NEMA 1 Enclosure
KEB, Kinetic Energy Buffering
Fire Mode
Built-in Five Relay Outputs
Real Time Clock
H100 Bypass
HVAC/PUMP Application
North America Tel : 800-981-2941 customer_care.us@lsis.com |
HEAD OFFICE LS Tower, 127, LS-ro, Dongan-gu, Anyang-si, Gyeonggi-Do, 431-848, Korea |
Tel : 82-2-2034-4620 mswoo@lsis.com
Tel : 82-2-2034-4907 hjchoi@lsis.com
2016. 12 Specifications in this catalog are subject to change without notice due to continuous product development and improvement. H100 Bypass (E)_2016. 01 / (02) 2016.12 Printed in Korea_HumanPower
Block Diagram
Standard Specification
Dimension
• The standard motor capacity is based on a standard 4-pole motor.
• The standard used for 200V inverters is based on a 220V supply voltage.
and 400V inverters are based on a 460V supply voltage.
• The standard output current is limited based on the carrier frequency set at CON-04.
[Units : mm(inches)]
3-Phase 200V Class 5.5~18.5kW (7.5~25HP)
Model□□□□SP100-2□□□ | 0055 | 0075 | 0110 | 0150 | 0185 | |
Applied Motor | HP | 25 | 7.5 | 10 | 15 | 20 |
kW | 18.5 | 5.5 | 7.5 | 11 | 15 |
3-Phase 400V Class 5.5~18.5kW (7.5~25HP)
Model□□□□SP100-4□□□ | 0055 | 0075 | 0110 | 0150 | 0185 | |
Applied Motor | HP | 25 | 7.5 | 10 | 15 | 20 |
kW | 18.5 | 5.5 | 7.5 | 11 | 15 |
3-Phase 400V Class 22~55kW (30~75HP)
Model□□□□SP100-4□□□ | 0220 | 0300 | 0370 | 0450 | 0550 | |
Applied Motor | HP | 75 | 30 | 40 | 50 | 60 |
kW | 55 | 22 | 30 | 37 | 45 |
H1
D1
H2
W D3
D2
Model | H2 | W | D1 | D2 | D3 | H1 | |
3-phase 200V Class |
0055SP100-2 | 517.3 (20.36) |
750.1 (29.53) |
158.3 (6.23) |
217.5 (8.56) |
181 (7.13) |
174 (6.85) |
3-phase 400V Class |
0055SP100-4 | 517.3 (20.36) |
750.1 (29.53) |
158.3 (6.23) |
217.5 (8.56) |
181 (7.13) |
174 (6.85) |
0075SP100-2 | |||||||
0110SP100-2 | 684.3 (26.94) |
998.7 (39.31) |
197.7 (7.78) |
260.8 (10.26) |
224.8 (8.85) |
217.7 (8.57) |
|
0150SP100-2 | |||||||
0075SP100-4 | |||||||
0110SP100-4 | |||||||
0150SP100-4 | 684.3 (26.94) |
998.7 (39.31) |
197.7 (7.78) |
260.8 (10.26) |
224.8 (8.85) |
217.7 (8.57) |
|
0185SP100-4 | |||||||
0220SP100-4 | 758.8 (29.87) |
1132 (44.56) |
237.7 (9.35) |
287.8 (11.33) |
253.2 (9.97) |
244.7 (9.63) |
|
0300SP100-4 | |||||||
0370SP100-4 | 912.2 (35.91) |
1460 (57.48) |
327 (12.87) |
342 (13.46) |
304 (11.97) |
291 (11.45) |
|
0450SP100-4 | |||||||
0550SP100-4 | |||||||
0185SP100-2 | 758.8 (29.87) |
1132 (44.56) |
237.7 (9.35) |
287.8 (11.33) |
253.2 (9.97) |
244.7 (9.63) |
Items | Name | Description |
Regulated 3-phase output power to the motor | SP100 Output to Motor | U, V, W |
No additional wiring is required | Inverter Line Power Input | R’, S’, T’ |
No additional wiring is required | Inverter Output to Motor | U’, V’, W’ |
Input Contactor for the inverter mode | Input Contactor | MC3 |
Bypass Contactor for the inverter mode | Bypass Contactor | MC2 |
Output Contactor for the inverter mode | Output Contactor | MC1 |
3-phase AC line power supply to the adjustable frequency drive |
SP100 Line Power Input | R, S, T |
Items | Name | Description |
AC Reactor (Option) |
AC Reactor | AC Reactor for the inverter mode |
DC Reactor (Option) |
DC Reactor | DC Reactor for the inverter mode |
Circuit breaker for the SP100 input connections |
CB | Manual Motor Starters |
Protects inverter from motor overload, open phase and restraint |
Thermal Overload Relays |
OL Detector |
Power
Supply
3 Phase
60Hz
CB MC3
AC Reactor
(Option)
MC2
Bypass
Interlock
OL Detector
Motor
(Customer Supplied)
MC1
Inverter
DC Reactor
(Option)
H100
Control to
Sheet
R S T
R’
S’
T’
U’
V’
W’
U V W