Chapter 17 AB: EtherNet/IP
17-1 |
Chapter 17 AB: Control/CompactLogix, MicroLogix Series (EtherNet/IP)
It is only available for the following service versions or later.
Please download it from LSELECTRIC website and re-install it.
Controller name | Service version | Details |
Rockwell: EtherNet/IP ControlLogix/CompactLogix Series Native Rockwell: EtherNet/IP MicroLogix Series |
XP-Builder Ver2.11 | Web site: http://www.lselectric.co.kr/ |
17.1 Available PLC
PLC Type | CPU Module | Connection mode |
Communication mode |
Connection Module |
Remarks |
CompactLogix | 1769 CompactLogix | EtherNet/IP | Ethernet | 1769-L32E 1769-L35E 1768-ENBT |
RSLogix5000 (Programming software) |
ControlLogix | 1768 CompactLogix | 1756-EN2T 1756-EN2F 1756-ENBT |
|||
MicroLogix | MicroLogix1000 | EtherNet/IP | Ethernet | 1761-NET-ENI | RSLogix500 |
Notice |
(1) Not available PLC ► Connection problem may occur depending on module O/S version. (2) Programming Tool ► RSLogix5000 – Controlling, CompactLogix ► RSLogix500 – PLC-5, SLC500, MicroLogix |
Chapter 17 AB: EtherNet/IP
17-2 |
17.2 Control/CompactLogix Series (EtherNet/IP)
17.2.1 Connection
The device area is tag type under Control/CompactLogix series so a user needs to define tag directly.
To apply the tag defined by a used to XP-Builder, L5K or CSV file should be created.
No | Setup Process |
How to setup |
1 | Creating File (1) |
|
After executing RSLogix5000 program, select the menu [Communication] – [Who Active]. | ||
2 | Creating File (2) |
|
After connecting to the PLC, save the created controller tag (Save as file extension L5K) |
Chapter 17 AB: EtherNet/IP
17-3 |
Notice |
1) Suggestions ► For setting PLC communication or creating tag, refer to RSLogix5000 manual. ► Program Tag: External access is not allowable through Program local Tag -> in the case of applying to XP, error occurs. ► Bit Offset and continuous reading are available for BOOL Array or Access area only. ► CSV File Import: The function will be added afterward. |
17.2.2 Communication Setting
Select the menu [Common]-[Project Property] → [Device Setting]-[Detailed connection option setting]
No | Setup Process |
How to setup |
1 | Communi cation Setting |
|
Select the menu [Common]-[Project Property] → [Device Setting]-[Detailed connection option setting] |
Chapter 17 AB: EtherNet/IP
17-4 |
No | Setup Process |
How to setup |
2 | Communi cation Setting (2) |
|
After inputting the IP address of PLC EtherNet/IP to be connected, import the created file. |
Notice |
1) Suggestions ► Slot No.: designates the slot No. of CPU. (Not slot No. of communication module) ► It can be applied only when Tag list is already declared or imported. |
Chapter 17 AB: EtherNet/IP
17-5 |
17.3 MicroLogix Series (EtherNet/IP)
17.3.1 Connection
No | Setup Process |
How to setup |
1 | Communi cation Setting (1) |
|
After executing RSLogix500 program, select the menu [Comms] – [Who Active Go Online]. | ||
2 | Communi cation Setting (2) |
|
If you click [Create New File], connection process is completed. |
Notice |
1) Suggestions ► For setting PLC communication, refer to RSLogix500 manual. |
Chapter 17 AB: EtherNet/IP
17-6 |
17.3.2 Communication Setting
No | Setup Process |
How to setup |
1 | Communi cation Setting (1) |
|
Select the menu [Common]-[Project Property] → [Device Setting]-[ Detailed connection option setting ] | ||
2 | Communi cation Setting (2) |
|
Input the IP address of PLC EtherNet/IP module to be connected. |
Chapter 17 AB: EtherNet/IP
17-7 |
17.3.3 Device Nomenclature
It indicates the device configuration of MicroLogix under XP-Builder and offset address is set to the number of digits.
Data Type | PLC | XP-Builder |
Bit Integer File Bit File Input File Output File |
N7:12/11 File Type File Number Element Bit |
N00701211 File Type File Number (3 digits) Element (3digits) Bit (2digits) |
Word Integer File Bit File Input File Output File |
N7:123 File Type File Number Element |
N007123 File Type File Number (3digits) Element (3digits) |
Bit/Word Timer File Counter File Controller File Floating Point File String File ASCII File |
T4:0/EN File Type File Number Element Sub Element |
TEN004012 File Type File Number (3digits) Element (3digits) Sub Element |
Chapter 17 AB: EtherNet/IP
17-8 |
17.4 Available Device
The available devices for XGT Panel are as below.
17.4.1 Control/CompactLogix Series
Type | Type Code | Description |
SINT | C2 | Signaled 8 Bit |
INT | C3 | Signaled 16Bit |
DINT | C4 | Signaled 32Bit |
LINT | C5 | Signaled 64Bit |
USINT | C6 | Non-Signaled 8Bit |
UINT | C7 | Non-Signaled 16Bit |
UDINT | C8 | Non-Signaled 32Bit |
ULINT | C9 | Non-Signaled 64Bit |
REAL | CA | 32 Bit real number |
LREAL | CB | 64 Bit real number |
STRING | D0 | Character string (1 byte/character) |
BYTE | D1 | 8 Bit String |
WORD | D2 | 16 Bit String |
DWORD | D3 | 32 Bit String |
LWORD | D4 | 64 Bit String |
BOOL | C1 | Bit |
Notice |
(1) Suggestions ► Available Tag for Bit Address: Only the SINT, INT, DINT are available for Bit Address of the Tag that is not BOOL type. ► When applying SINT type to 16 bit under XP-Builder, only sub-byte is displayed, wiring is allowed. ► Only the tag declared through Array is available for continuous reading(data list, character string, recipe, device to be logged) ► Reading continuous bit is available within internal bit size such as BOOL Array type or DINT. (DINT tag1.0 ~ tag1.31) ► LINT type is displayed to the lower 32 bit (The maximum device size of XP is 32 bit) ► In case of STRING type, "Multi Copy" function does not work properly. |
Chapter 17 AB: EtherNet/IP
17-9 |
17.4.2 MicroLogix Series
Device | Bit Address | Word Address | Remarks | |||
Input File | I0:0/00 ~ I63:255/15 | I0:0 ~ I63:255 | - | |||
Output File | O0:0/00 ~ O63:255/15 | O0:0~O63:255 | - | |||
Status File | S2:0/0 ~ S2:163/15 | S2:0 ~ S2:163 | - | |||
Binary File | B3:0/0 ~ B3:255/15 B9:0/0 ~ B255:255/15 |
B:3:0 ~ B3:255 B9:0 ~ B255:255 |
- | |||
Timer File | Enable | T4:0/ ~ T4:255/ T9:0/ ~ T255:255 |
EN | T4:0. ~ T4:255. T9:0. ~ T255:255. |
- | - |
Timing | TT | - | - | |||
Done | DN | - | - | |||
Preset | - | PRE | - | |||
Accumulated | - | ACC | - | |||
Counter File |
Up Enable | C5:0/ ~ C5:255/ C9:0/ ~ C255:255/ |
CU | C5:0. ~ C5:255. C9:0. ~ C255:255. |
- | - |
Down Enable | CD | - | - | |||
Done | DN | - | - | |||
Overflow | OV | - | - | |||
Underflow | UN | - | - | |||
Update Acc | UA | - | - | |||
Preset | - | PRE | - | |||
Accumulated | - | ACC | - | |||
Control File |
Enable | 6:0/ ~ R6:255/ R9:0/ ~ R255:255/ |
EN | R6:0. ~ R6:255. R9:0. ~ R255:255. |
- | - |
Enable Unload | EU | - | - | |||
Done | DN | - | - | |||
Empty | EM | - | - | |||
Error | ER | - | - | |||
Unload | UL | - | - | |||
Inhibit Comp. | IN | - | - | |||
Found | FD | - | - | |||
Length | - | LEN | - | |||
Position | - | POS | - | |||
Integer File | N7:0/0 ~ N7:255/15 N9:0/0 ~ N255:255/15 |
N7:0 ~ N7:255 N9:0 ~ N255:255 |
- | |||
Floating Point File | - | F8:0 ~ F8:255 F9:0 ~ F255:255 |
32 Bit | |||
String File | - | ST9:0 ~ ST255:255 | - | |||
LONG File | - | L9:0 ~ L255:255 | 32 Bit |
Notice |
(1) Suggestion ► In the case of applying unavailable address, Error occurs: 0x10 ► F, ST, L files can not be added under MicroLogix1000series (can be added under MicroLogix1200, MicroLogix1500 series). |
Chapter 17 AB: EtherNet/IP
17-10 |
17.5 EDS File
An EDS (Electric Data Sheet) file is required to register XGT Panel as an EtherNet / IP device in the network.
The location of the EDS file is in the following path under the folder where XP-Builder is installed.
17.5.1 EDS file location
No | Setup Process |
How to setup |
1 | <XP-Builder]-[Controllers]-[ROCK_EIP]-[EDS]> <Before registering the device as the EDS file> <After registering device with the EDS file> |
Chapter 17 AB: EtherNet/IP
17-11 |
17.5.2 How to register for EDS
Here is how to register EDS file on your PC.
No | Setup Process |
How to setup |
1 | <the guideline from "RSLinx Classic Help"> |
Chapter 17 AB: EtherNet/IP
17-12 |
No | Setup Process |
How to setup |
2 |
Chapter 17 AB: EtherNet/IP
17-13 |
Chapter 17 AB: EtherNet/IP
17-14 |
Follow the instructions in the "EDS Hardware Installation Tool" to register the EDS file. |