2

● M100 4
● G100 5
● S100 6
● H100 7
● iE5 8
● iG5A 9

● iS7 10
● iP5A 11
● iV5 12
● Comparison 13
● Option list 15

Contents

200/400V 11~22kW is scheduled to be release in 2020.

3Ø 200V : 2.2kW~37kW
3Ø 400V : 2.2kW~800kW

3Ø 200V : 0.75kW~75kW
3Ø 400V : 0.75kW~375kW

3Ø 200V : 5.5kW~30kW
3Ø 400V : 5.5kW~450kW
3Ø 575V : 5.5kW~280kW

3Ø 200V : 5.5kW~18.5kW
3Ø 400V : 5.5kW~500kW

1Ø 200V : 0.4kW~2.2kW
3Ø 200V : 0.4kW~15kW
3Ø 400V : 0.4kW~75kW

1Ø 200V : 0.4kW~1.5kW
3Ø 200V : 0.4kW~22kW
3Ø 400V : 0.4kW~22kW

3Ø 200V : 0.4kW~7.5kW
3Ø 400V : 0.4kW~7.5kW

1Ø 200V : 0.1kW~0.4kW
3Ø 200V : 0.1kW~0.4kW

1Ø 200V : 0.1kW~2.2kW

LS Drive Series 3

4

Variable Frequency Drive

M100 1 phase 0.1 ~ 2Ultra Compact Micro VFD

.2kW (0.125 ~ 3.0HP), 200 ~ 240V

● Built-in EMC filter (C2 Class)
● Compact & Micro size
● DIN rail installation
● Side by side installation (2mm)
● Potenciometer
● Built-in RS485 communication (Advanced model)
● Built-in DB Unit (1.5kW or higher)
● Easy connection with RJ 45 port
(Modbus, Smart Copier, Remote keypad, DriveView 7)
● CE and New UL 61800-5-2 design

Model Number
LSLV 0008 M100 - 1
Input Voltage
1 : 1-phase, 200 ~ 240V

Keypad
E : LED keypad

EMC filter
F : Built-in EMC filter

I/O
S: Standard I/O
A: Advanced I/O

Reactor
N: Non-Reactor

UL type
O : UL open (IP20)

Sereis name
M100

LS Low Voltage
Drive Series

Rated Motor (kW)
0001 : 0.1kW~0022:2.2kW

E O F N S

General specification

Control Spec. Control method V/F control, slip compensation
Frequency settings power
resolution

Digital command: 0.01Hz
Analog command: 0.06 Hz (60 Hz standard)
Frequency accuracy 1% of maximum output frequency
V/F pattern Linear, square reduction, user V/F
Overload capacity Rated current: 150% 1 min
Torque boost Manual torque boost, automatic torque boost
Operation Operation type Select key pad, terminal strip, or communication operation
Frequency settings Analog type: V1terminal 0–10 V, I2 terminal (Advanced I/O) 0–20 mA and 0–10 V

Digital type: key pad input
Operation function Anti-forward and reverse direction rotation, Frequency jump, Frequency limit, DC braking, Jog operation, Up-down operation, 3-wire operation, Dwell operation,

Slip compensation, PID control, Energy saving operation, Speed search, Automatic restart

Input signal

Multi-function terminal

Select PNP (Source) or NPN (Sink) mode.
Forward direction operation, Reset, Emergency stop, Multi-step speed frequency-high/med/low, DC braking during stop, Frequency increase, 3-wire, Select acc/dec/
stop, Reverse direction operation, External trip, Jog operation, Multi-step acc/dec-high/med/low, Second motor selection, Frequency reduction, Fix analog command
frequency, Transition from PID to general operation

Output signal tMulti- function open collector

erminal (standard I/O only) Fault output and inverter operation status output Less than DC 24 V, 50 mA
Multi-function relay terminal Less than (N.O., N.C.) AC250V 1A, Less than DC 30V, 1A
Analog output 0–10 Vdc: Select frequency, output current, output voltage, DC terminal voltage and others
Protection Failures Motor over heat trip, Motor overload trip, Output open-phase trip, External signal trip, Inverter overload trip, Command loss trip Over current trip, Inverter over heat,

Over voltage trip, Ground trip, COM trip, Fan trip, Low voltage trip, Command loss trip
Alerts Overload alarm
Instantaneous blackout

Less than15 ms: continue operation (must be within the rated input voltage and rated output range)
More than 15 ms: auto restart operation
Enclosure IP20

Model number: LSLV M100-1EOFN 0001 0002 0004 0008 0015 0022
Motor rating [HP] 0.125 0.25 0.5 1 2 3
[kW] 0.1 0.2 0.4 0.75 1.5 2.2
Output rating Rated Capacity [kVA] 0.3 0.6 0.95 1.9 3 4.5
Rated Current [A] 0.8 1.4 2.4 4.2 7.5 10
Output Frequency 0–400 Hz
Output Voltage [V] 3-phase 200–240 V
Input rating Service Voltage [V] 3-phase 200–240 V (-15%~+10%)
Input Frequency 50–60 Hz (±5%)
Rated Current [A] 1 1.8 3.7 7.1 13.6 18.7
Weight [kg] 0.66 1 1.45

LS Inverter Series 5

Variable Frequency Drive

G100 3 phase 0.4~7.5kWGeneral Drive VFD

(0.5~10HP), 200~400V
3 phase 0.4~7.5kW(0.5~10HP), 380~480V

● Meets UL 61800-5-1
● Military (MIL 217Plus) design based methodology
● Enhanced materials and manufacturing processes
● Enhanced motor control-sensorless & V/F performance
● User-friendly-easy tuning sensorless control
● Suitable for most applications
● Easy to install, use and maintain
● Various options

LSLV 0008 G100 - 4 E O F N
LS Low Voltage
Drive Series

Motor rating(kW)
0004: 0.4kW ~ 0220: 2.2kW

Series name
G100

Input Voltage
2 : 3-phase 200 ~ 240[V]
4 : 3-phase 380 ~ 480[V]

Keypad
E : LED Keypad

UL Type
O : UL Open

EMC Filter
F : Built-in EMC
N : Non-EMC

Reactor
N : Non-reactor

Model Number

General specification
Model number: LSLV G100-2 0004 0008 0015 0022 0040 0055 0075
Motor
Rating

Heavy Duty (HD) (HP) 0.5 1.0 2.0 3.0 5.4 7.5 10

(kW) 0.4 0.75 1.5 2.2 4.0 5.5 7.5
Normal Duty (ND) (HP) 1.0 2.0 3.0 5.4 7.5 10 15

(kW) 0.75 1.5 2.2 4.0 5.5 7.5 11

Output
Rating

Capacity [kVA] Heavy Duty (HD) 1.0 1.9 3.0 4.2 6.5 9.1 12.2

Normal Duty (ND) 1.2 2.3 3.8 4.6 6.9 11.4 15.2

Rated Current
(3-Phase Input) [A]

Heavy Duty (HD) 2.5 5.0 8.0 11.0 17.0 24.0 32.0
Normal Duty (ND) 3.1 6.0 9.6 12.0 18.0 30.0 40.0

Rated Current
(1-Phase Input) [A]

Heavy Duty (HD) 1.5 2.8 4.6 6.1 9.3 12.8 17.4
Normal Duty (ND) 2.0 3.6 5.9 6.7 9.8 16.3 22.0
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 200~240V

Input
Rating

Voltage [V] 3-Phase 200~240VAC (-15%~+10%)
Frequency [Hz] 50~60Hz (±5%)
Rated Current [A] Heavy Duty (HD) 2.2 4.9 8.4 11.8 18.5 25.8 34.9

Normal Duty (ND) 3.0 6.3 10.8 13.1 19.4 32.7 44.2
Weight [kg] 1.04 1.06 1.36 1.4 1.89 3.08 3.21

Control Control Method V/F, Slip Compensation, Sensorless Vector
Frequency Setting Resolution Digital command: 0.01Hz / Analog command: 0.06Hz(maximum frequency: 60 Hz)
Frequency Accuracy 1% of the maximum output frequency
V/F Pattern Linear, squared, user V/F
Overload Capacity HD: 150% 1 minute, ND: 120% 1minute
Torque Boost Manual/Automatic torque boost
Operation Operation Mode Select key pad, terminal strip, or communication operation
Frequency Setting Analog: -10~10[V], 0~10[V], 4~20[mA] / Digital: Keypad
Operation Function PID control, 3-wire operation, Frequency limit, Second function, Anti-forward and reverse direction rotation, Commercial transition, Speed search, Power braking, Leakage
reduction, Up-down operation, DC braking, Frequency jump, Slip compensation, Automatic restart, Automatic tuning, Energy buffering, Flux braking, Fire mode
Input Multi-Function
Terminal
(5 Points)

NPN (Sink) / PNP (Source) Selectable
Function: Forward run, Reverse run, Reset, External trip, Emergency stop, Jog operation, Multi-step frequency-high, middle, low, Multi-step acceleration/ deceleration-high,
middle, low, DC braking at stop, 2nd motor select, Frequency up/down, 3-wire operation, Change into normal operation during PID operation, Change into main body
operation during option operation, Analog command frequency fixing, Acceleration/deceleration stop etc. Selectable
Analog Input V1: -10~10V, I2 4~20mA
Output Multi-function Relay Terminal Fault output and drive operation status output (N.O., N.C.) less than AC 250V 1A, less than DC 30V 1A
Analog Output 0~12Vdc: Frequency, Output current, Output voltage, DC stage voltage etc. selectable

Protective
Function

Trip Over current trip, external signal trip, ARM short current fault trip, over heat trip,
input imaging trip, ground trip, motor over heat trip, I/O board link trip, no motor trip,
parameter writing trip, emergency stop trip, command loss trip, external memory
error, CPU watchdog trip, motor light load trip

Over voltage trip, temperature sensor trip, inverter over heat, option trip, output
image trip, inverter overload trip, fan trip, pre-PID operation failure external brake
trip, low voltage trip during operation, low voltage trip, analog input error, motor
overload trip, over torque trip, under torque trip
Alam Command loss trip warning, overload warning, light load warning, inverter overload warning, fan operation warning, braking resistance braking rate warning, rotor time
constant tuning error, inverter pre-overheat warning, over torque warning, under torque warning
Momentary Power Loss HD below 15ms (ND below 8ms): Continuous operation (To be within rated input voltage, rated output) HD above 15ms (ND above 8ms): Automatic restart operation enable
Environment Cooling Type Forced fan cooling structure
Protection Degree IP20/UL Open (Default), UL Enclosed type 1 (Option)
Ambient Temperature Ambient temperature under the condition of no ice or frost. HD: -10~50℃(14~122°F) / ND: -10~40℃(14~104°F)
[However, recommended to use load below 80% when using at 50°C under light load]
Humidity Relative humidity below 95% RH (no dew formation)
Storage Temperature -20~65℃(-4~149°F)
Location No corrosive gas, flammable gas, oil mist and dust etc. indoors (Pollution degree 2 environment)
Altitude, Vibration Below 1,000m (From 1000 to 4000m, the rated input voltage and rated output current of the drive must be derated by 1% for every 100m.), below 9.8m/sec2 (1G)
Pressure 70~106kPa

Model number: LSLV G100-4 0004 0008 0015 0022 0040 0055 0075
Motor
Rating

Heavy Duty (HD) (HP) 0.5 1.0 2.0 3.0 5.4 7.5 10

(kW) 0.4 0.75 1.5 2.2 4.0 5.5 7.5
Normal Duty (ND) (HP) 1.0 2.0 3.0 5.4 7.5 10 15

(kW) 0.75 1.5 2.2 4.0 5.5 7.5 11

Output
Rating

Capacity [kVA] Heavy Duty (HD) 1.0 1.9 3.0 4.2 6.5 9.1 12.2

Normal Duty (ND) 1.5 2.4 3.9 5.3 7.6 12.2 17.5

Rated Current
(3-Phase Input) [A]

Heavy Duty (HD) 1.3 2.5 4.0 5.5 9.0 12.0 16.0
Normal Duty (ND) 2.0 3.1 5.1 6.9 10.0 16.0 23.0

Rated Current
(1-Phase Input) [A]

Heavy Duty (HD) 0.7 1.4 2.1 2.8 4.9 6.4 8.7
Normal Duty (ND) 1.3 1.9 2.8 3.6 5.4 8.7 12.6
Frequency [Hz] 0~400Hz (IM sensorless: 0~120Hz)
Voltage [V] 3-Phase 380~480V

Input
Rating

Voltage [V] 3-Phase 380~480VAC (-15%~+10%)
Frequency [Hz] 50~60Hz (±5%)
Rated Current [A] Heavy Duty (HD) 1.1 2.4 4.2 5.9 9.8 12.9 17.5

Normal Duty (ND) 2.0 3.3 5.5 7.5 10.8 17.5 25.4
Weight [kg] 1.02 1.06 1.4 1.42 1.92 3.08 3.12

• Maximum applicable capacity is indicated in case of using a 4-pole standard motor
• For the rated capacity, 200 and 400V class input capacities are based on 220 and 440V, respectively.
• The rated output current is limited based on the carrier frequency set at Cn.04.

• The output voltage becomes 20-40 % lower during no-load operations to protect the inverter from the
impact of the motor closing and opening (0.4-4.0 kW models only).

6

Variable Frequency Drive

S100 High Performance Standard VFD

1 phase 0.4~2.2kW(0.5~3HP), 200~240V
3 phase 0.4~15kW(0.5~20HP), 200~240V
3 phase 0.4~75kW(0.5~100HP), 380~480V
● Selectable V/f, Sensorless vector control
● Built-in EMC Filter
● Side by Side Installation
● Enhanced Size Competitiveness
● PLC Function(Simple Sequence Operation)
● Compliance with Open Field Networks
- Profibus-DP, CANopen, EtherNet
● IP66 Enclosure (0.4~22kW)
● PM Sensorless Control
● P2P I/O Share Function
● Capacitor/Fan Life Cycle Management Function
● Smart Copier Option
(Able to copy parameter and download drive main OS)

General specification

LSLV 0008 S100 - 2 E O F D
LS Low Voltage
Drive Series

Motor rating(kW)
0004: 0.4kW ~ 0750: 75kW

Series name
S100

Input Voltage
1 : 1-phase 200 ~ 240[V]
2 : 3-phase 200 ~ 240[V]
4 : 3-phase 380 ~ 480[V]

Keypad
E : LED Keypad
C : LCD Keypad

UL Type
O : UL Open
X : IP66

EMC Filter
F : Built-in EMC
N : Non-EMC

Reactor
D : Built-in DCL
N : Non-Reactor

S

I/O
M : Multiple (3.5mm)
S : Standard (5mm)

Model number: LSLV S100-4 0004 0008 0015 0022 0037 0040 0055 0075 0110 0150 0185 0220 0300 0370 0450 0550 0750
Motor rating Heavy [HP] 0.5 1.0 2.0 3.0 5.0 5.5 7.5 10.0 15.0 20.0 25

.0 30.0 40.0 50.0 60.0 75.0 100.0
Duty(HD) [kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0

Normal [HP] 1.0 2.0 3.0 5.0 5.4 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0 100.0 120.0
Duty(HD) [kW] 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Output rating Capacity Heavy Duty(HD) 1.0 1.9 3.0 4.2 6.1 6.5 9.1 12.2 18.3 22.9 29.7 34.3 46.5 57.2 69.4 83.8 115.8
[kVA] Normal Duty(ND) 1.5 2.4 3.9 5.3 7.6 7.6 12.2 17.5 22.9 29.0 33.5 44.2 57.2 69.4 81.5 108.2 128.8
Rated Heavy Duty(HD) 1.3 2.5 4.0 5.5 8.0 9.0 12.0 16.0 24.0 30.0 39.0 45.0 61.0 75.0 91.0 110.0 152.0
Current Normal Duty(ND) 2.0 3.1 5.1 6.9 10.0 10.0 16.0 23.0 30.0 38.0 44.0 58.0 75.0 91.0 107.0 142.0 169.0
Frequency [Hz] 0~400Hz (IM Sensorless:0~120[Hz])
Voltage [V] 3-phase 380 ~ 480V
Input rating Voltage [V] 3-phase 380 ~ 480VAC (-15%~+10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Rated Heavy Duty(HD) 1.1 2.4 4.2 5.9 8.7 9.8 12.9 17.5 26.5 33.4 43.6 50.7 56.0 69.0 85.0 103.0 143.0
Current[A] Normal Duty(ND) 2.0 3.3 5.5 7.5 10.8 10.8 17.5 25.4 33.4 42.5 49.5 65.7 69.0 85.0 100.0 134.0 160.0
Weight[kg] (Built-in EMC) 0.9(1.18) 1.9(1.18) 1.3(1.77) 1.5(1.80) 2.0(2.23) 2.0(2.23) 3.3 3.4 4.6 4.8 7.5 7.5 25.8 34.4 34.4 41.8 43.8
Control spec Control method V/f, Slip compensation, Sensorless vector
Speed reference resolution Digital command: 0.01Hz / Analog command: 0.06Hz (Maximum frequency : 60Hz)
Frequency accuracy 1% of the maximum output frequency
V/f curve Linear, Squared, User V/F
Overload capacity HD: 150% 1minute, ND: 120% 1minute
Torque boost Manual/Automatic torque boost
Operation Keypad display 4 digit, 7 segment LED keypad
Operation method Keypad / Terminal / Communication option selectable
Frequency setting Analog: -10 -10[V] / 0 -10[V], 420[mA] / Digital: Keypad, Pulse train input
Operation function PID, Up-Down, 3-Wire, DC braking, Frequency limit, Frequency jump, 2nd function, Slip compensation, Anti reverse rotation, Automatic restart, Commercial power change, Auto-tuning,
Flying start, Energy buffering operation, Power braking, Flux braking, Leakage reduction operation
Input signal Multi-function terminal NPN(Sink) / PNP(Source) selectable
Standard I/O(5points) Function: Forward run, Reverse run, Reset, External trip, Emergency stop, Jog operation, Multi-step frequency-high, middle, low, Multi-step acceleration/deceleration-high, middle, low,
Multiple I/O(7points) DC braking at stop, 2nd motor select, Frequency up/down, 3-wire operation, Change into normal operation during PID operation, Change into main body operation during option operation,
Analog command frequency fixing, Acceleration/deceleration stop etc. selectable
Pulse train 0Hz~32Hz, Low level: 0~0.8V, High level: 3.5~12V
Output signal Open collector terminal Fault output and drive operation status output
Multi-function relay (N.O., N.C.) less than AC 250V 1A, less than DC30V 1A
Analog output 0 to 10Vdc (4~20mA): Frequency, Output current, Output voltage, DC stage voltage etc. selectable
Pulse train Maximum 32kHz, 10~12[V]
Protection Drive trip Overcurrent / Overvoltage / Undervoltage / External trip / Ground fault current detection / Drive overheat / Motor overheat / Input-Output phase open / Overload protection /
Light load protection / Communication error / Frequency command loss / Hardware fault / Cooling fan fault / Pre-PID motion failure / No motor trip / External brake trip / Option fault /
Safety contact fault / Drive temperature sensor fault / Parameter write error / IO board fault
Drive alarm Stall prevention / Overload / Light load / Cooling fan fault / Frequency command loss / DB duty cycle / Rotor time constant tuning fault / Capacitor / Fan life time up
Enclosure IP20, UL Type1, IP66
Option Keypad Graphic LCD keypad(iS7)
Communication Profibus-DP, EtherNet-IP, Modbus-TCP, CANopen

Model number: LSLV S100-2 0004 0008 0015 0022 0037 0040 0055 0075 0110 0150
Motor rating Heavy [HP] 0.5 1.0 2.0 3.0 5.0 5.5 7.5 10.0 15.0 20.0
Duty(HD) [kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11.0 15.0

Normal [HP] 1.0 2.0 3.0 5.0 5.4 7.5 10.0 15.0 20.0 25.0
Duty(HD) [kW] 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11.0 15.0 18.5
Output rating Capacity Heavy Duty(HD) 1.0 1.9 3.0 4.2 6.1 6.5 9.1 12.2 17.5 22.9
[kVA] Normal Duty(ND) 1.2 2.3 3.8 4.6 6.9 6.9 11.4 15.2 21.3 26.3
Rated Heavy Duty(HD) 2.5 5.0 8.0 11.0 16.0 17.0 24.0 32.0 46.0 60.0
Current Normal Duty(ND) 3.1 6.0 9.6 12.0 18.0 18.0 30.0 40.0 56.0 69.0
Frequency [Hz] 0~400Hz (IM Sensorless:0~120[Hz])
Voltage [V] 3-phase 200~240V
Input rating Voltage [V] 3-phase 200 ~ 240VAC (-15%~+10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Rated Heavy Duty(HD) 2.2 4.9 8.4 11.8 17.5 18.5 25.8 34.9 50.8 66.7
Current[A] Normal Duty(ND) 3.0 6.3 10.8 13.1 19.4 19.4 32.7 44.2 62.3 77.2
Weight[kg] (Built-in EMC) 0.9 0.9 1.3 1.5 2.0 2.0 3.3 3.3 4.6 7.1

Model number: LSLV S100-1 0004 0008 0015 0022
Motor rating Heavy [HP] 0.5 1.0 2.0 3.0
Duty(HD) [kW] 0.4 0.75 1.5 2.2

Normal [HP] 1.0 2.0 3.0 5.0
Duty(HD) [kW] 0.75 1.5 2.2 3.7
Output rating Capacity Heavy Duty(HD) 1.0 1.9 3.0 4.2
[kVA] Normal Duty(ND) 1.2 2.3 3.8 4.6
Rated Heavy Duty(HD) 2.5 5.0 8.0 11.0
Current Normal Duty(ND) 3.1 6.0 9.6 12.0
Frequency [Hz] 0~400Hz (IM Sensorless:0~120[Hz])
Voltage [V] 3-phase 200~240V
Input rating Voltage [V] 1-phase 200 ~ 240VAC (-15%~+10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Rated Heavy Duty(HD) 4.4 9.3 15.6 21.7
Current[A] Normal Duty(ND) 5.8 11.7 19.7 24.0
Weight[kg] (Built-in EMC) 0.9(1.14) 1.3(1.76) 1.5(1.76) 2.0(2.22)

Model Number

LS Inverter Series 7

Variable Frequency Drive

H100 3 phase 0.75~18.5kFan and Pump VFD

W(1.0~25HP), 200~240V
3 phase 0.75~500kW(1.0~800HP), 380~480V

● Specialized function for HVAC
- Multi-motor control
- Scheduling function
(Time event: Real Time Clock)
- Flow Compensation
- Soft fill operation
- Start Ramp & End Ramp
- Dec Valve Ramp
- Pump Clean
- Load Tuning
- Fire Mode
- Energy-saving Display (Payback Counter)
- Boost, Wake-up function

● V/f control
● Built-in BACnet communication
● LonWorks(Option)
● Keypad Exclusive for HVAC
● Built-in EMC filter/DC Reactor
● Side by Side Installation
● Heatsink out the back installation
(Flange Option)
● Enhanced Size Competitiveness
● Capacitor/Fan Life Cycle Management
Function
● Smart Copier Option
(Able to copy parameter and download
drive main OS)

General specification

LSLV 0055 H100 - 4 C O F N

LS Low Voltage
Drive Series

Motor rating(kW)
0008: 0.75kW ~ 5000: 500kW

Series name
H100

Input Voltage
2 : 3-phase 200~240[V]
4 : 3-phase 380~480[V]

Keypad Type
C : LCD Keypad

UL Type
O : UL Open
E : UL Type1

EMC Filter
F : Built-in EMC
N : Non EMC

Reactor
D : Built-in DC Reactor
N : Non DC Reactor

Model Number

Control Spec Control Method V/F control, slip compensation
Frequency Set Resolution Digital command: 0.01Hz
Analog command: 0.06Hz (based on 60Hz)
Control Degree of Frequency 1% of the maximum output frequency
V/f curve Liner, squared overload reduction and user V/F
Overload Capacity Rated Current: 120% , 1 minute (5.5~90kW), 110% , 1 minuite (110~500kW)
Torque Boost Manual torque boost, automatic torque boost 1, automatic torque boost 2
Operation Operation Method Optional: Keypad, terminal board or communication control
Frequency Setting Analog mode: -10~10V, 0~10V, 0~20mA
Digital mode: Keypad and pulse train input
Operation function PID control, 3-Wire control, Frequency limitation, Secondary Functions, Forward/Reverse rotation prohibited, DC braking, Commercial power switching, Speed search,
Power braking, Reduction of leakage, Up-Down control, DC braking Flux braking, Frequency pump, Slip compensation, Automatic restart, Automatic tuning, Energy buffering control,
Energy-saving control
Input signal Multifunctional Forward Operation, Reset, Emergency stop, Multi-step frequency – High/Mid/Low, DC braking during stop, Pre-Heat, Frequency increase, 3-Wire, Optional: Acceleration,
Terminal(7points) deceleration or stop, MMC interlock, Reverse Operation, Pump cleaning, External trip, Jog control, Multi-step acceleration/deceleration-High/Mid/Low, Secondary motor selection,
RTC(Time event function), Frequency decrease, Analog command frequency fixation, Switching to normal operation during PID operation
Pulse Train 0~3kHz, Low Level: 0~0.8V, High Level: 3.5~12V
Output signal Multifunctional Open DC 26V, 50mA or below

Collector Terminal
Failure [Fault] Relay Failure output & drive control status output: N.O. : AC 250V, 5A or below, DC30V, 3A or below

Terminal N.C. : AC 250V, 1A or below, DC30V, 1A or below
Multifunctional Relay Terminal AC 250V, 5A or below, DC30V, 5A or below
Analog Output 0~12Vdc(0~20mA): Optional among frequency, output current, output voltage and DC voltage
Pulse train Maximum 32kHz, 0~12V
Protection Trip Over-current trip, Trip caused by external signals, ARM short-circuit current trip, Overheat trip, Pipe broken trip, Input open-phase trip Ground trip, Motor overheat trip,
IO board connection trip, No Motor trip, Parameter Write trip, Emergency stop trip, Command loss trip, External memory error, CPU watchdog trip, Motor under-load trip, Overvoltage trip,
Temperature sensor trip, Drive overheat, Option trip, Output open-phase trip, Drive overload trip, Fan trip, Low voltage trip during operation, Low voltage trip, Analog input error,
Motor overload trip, Keypad command loss trip, Damper trip, Level Detect trip, All auxiliary motor failure trip, Pump clean failure (fault)
Warning Command loss trip warning, overload warning, under-load warning, drive overload warning, fan operation warning, damping resistance brake percentage warning, capacitor life warning,
pump clean warning, Fire Mode warning and LDT warning
Instant Power Below 8 ms: Continuous operation [within the rated input voltage and rated output]
Interruption 8 ms or above: Automatic restart operation
Enclosure IP20/UL Open(default), UL Enclosed Type 1(option)
Option Board Extension I/O (available soon)
Communication Lonworks
Others Built-in BACnet, Modbus-RTU(RS485), Metasys N2

Model number: H100-4
Applied Motor [HP]
Rated Output [kW]

Rated Capacity [kVA]
Rated Current
Output Frequency
Output Voltage [V]
Rated Input Service Voltage [V]
Input Frequency
Rated Current [A]
Weight [kg]

Model number: LSLV H100-2 0008 0015 0022 0037 0055 0075 0110 0150 0185
Applied Motor [HP] 1.0 2.0 3.0 5.0 7.5 10 15 20 25
Rated Output [kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5

Rated Capacity [kVA] 1.9 3.0 4.5 6.1 8.4 11.4 16.0 21.3 26.3
Rated Current 5 8 12 16 22 30 42 56 69
Output Frequency 0~400Hz
Output Voltage [V] 3-phase 200~240V
Rated Input Service Voltage [V] 3-phase 200~240VAC (-15%~+10%)
Input Frequency 50 ~ 60Hz (±5%)
Rated Current [A] 4.9 8.4 12.9 17.5 23.7 32.7 46.4 62.3 77.2
Weight [kg] 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.6 7.1
0008 0015 0022 0037 0055 0075 0110 0150 0185 0220 0300 0370 0450 0550 0750 0900 1100 1320 1600 1850 2200 2500 3150 3550 4000 5000
1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 60 75 100 120 150 200 250 300 350 400 500 550 650 800
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 220 250 315 355 400 500
1.9 3.0 4.5 6.1 9.1 12.2 18.3 23 29 34.3 46.5 57.1 69.4 82.0 108.2 128.8 170 201 248 282 329 367 467 520 587 733
2.5 4 6 8 12 16 24 30 38 45 61 75 91 107 142 169 223 264 325 370 432 481 613 683 770 962
0~400Hz
3-phase 380~480V 3-phase 380~500V
3-phase 380~480VAC (-15%~+10%) 3-phase 380~500VAC (-15%~+10%)
50 ~ 60Hz (±5%)
2.4 4.2 6.5 8.7 12.2 17.5 26.5 33.4 42.5 50.7 69.1 69.3 84.6 100.1 133.6 160.0 215.1 254.6 315.3 358.9 419.1 469.3 598.1 666.4 751.3 938.6
3.3 3.3 3.3 3.3 3.3 3.3 3.4 4.6 4.8 7.5 7.5 26 35 35 43 43 55.8 55.8 74.7 74.7 120.0 120.0 185.5 185.5 265 265

8

Variable Frequency Drive

iE5 User friendly micro size slim VFD

1 phase 0.1~0.4kW(0.1~0.5HP), 200~230V
3 phase 0.1~0.4kW(0.1~0.5HP), 200~230V

● V/f control
● Compact size: 68×128×85mm (2.7×5×3.3 inch)
● 0.1 ~ 200Hz frequency output
● 1 ~ 10kHz carrier frequency
● Fault history: Last 3 faults
● IP20 enclosure
● RS485 (LS Bus / Modbus RTU) communication (Built-in option)
● DC Injection braking
● Selectable manual/automatic torque boost
● Selectable PNP/NPN input signal
● PI control
● Up-Down & 3-Wire operation
● Automatic restart after instantaneous power failure
● Built-in potentiometer
● Monitoring & commissioning PC based software tool (Drive View)
● Parameter copy unit

General specification

Model Number

Model number: SV iE5- 001-1 002-1 004-1 001-2 002-2 004-2
Motor rating [HP] 0.13 0.25 0.5 0.13 0.25 0.5
[kW] 0.1 0.2 0.4 0.1 0.2 0.4
Output rating Capacity [kVA] 0.3 0.6 0.95 0.3 0.6 1.14
Current [A] 0.8 1.4 2.5 0.8 1.6 3.0
Voltage [V] Three-phase 200 ~ 230V
Frequency [Hz] 0.1 ~ 200Hz
Input rating Voltage [V] Single-phase 200 ~ 230V (±10%) Three-phase 200 ~ 230V (±10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Current [A] 2.0 3.5 5.5 1.2 2.0 3.5
Weight [kg] 0.44 0.46 1.68 0.43 0.45 0.67
Control spec Control method V/f, Slip compensation
Speed reference resolution Digital command: 0.01Hz / Analog reference: 0.1Hz (Max freq., 60Hz)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared V/f
Overload capacity 150% for 1 minute
Torque boost Auto & manual torque boost
Operation Keypad display 4 digit, 7 segment LED
Operation method Keypad / Terminal / Communication
Frequency setting Analog: 0 to 10V / 0 to 20mA / Potentiometer / Digital: Keypad
Operation function PI control / Up-Down operation / 3-Wire operation
Input signal Multi-function terminal PNP / NPN selectable
(P1 ~ P5) 5 points (programmable)
Output signal Multi-function relay Fault output & drive status output (N.O., N.C.) Less than AC 250V, 0.3A / Less than DC 30V 1A
Analog output 0 to 10Vdc (less than 10mA): frequency / current / voltage / DC voltage selectable
Protection Drive trip Over voltage / Low voltage / Over current / Ground fault / Drive overload / Overload trip / Drive overheat /
Condenser overload / Output phase open / Frequency command loss / Hardware fault / etc.
Drive alarm Stall prevention
Enclosure IP20
Option Communication, copy unit RS485(LS Bus / Modbus RTU), Parameter copy unit

SV 004 iE5 - 1 C

LS drive brand Motor rating
001: 0.1kW ~ 004: 0.4kW

Series name
iE5

Symbol Input rating
1 Single-phase, 200~230V
2 Three-phase, 200~230V

Symbol Communication
None Not available
C RS485 (LS Bus / Modbus RTU)

LS Inverter Series 9

Variable Frequency Drive

iG5A Powerful & compact sensorless vector control VFD

1 phase 0.4~1.5kW(0.5~2HP), 200~230V
3 phase 0.4~22kW(0.5~30HP), 200~230V
3 phase 0.4~22kW(0.5~30HP), 380~480V

● Selectable V/f, sensorless vector control
● Motor parameter Auto-tuning
● Powerful torque at overall speed range
● 0.1 ~ 400Hz frequency output
● 1 ~ 15kHz carrier frequency
● -15% ~ +10% input voltage margin
● Fault history: Last 5 faults
● 0~10Vdc / -10~+10Vdc analog input
● IP20 enclosure, UL Type 1 (Option)
● Selectable manual/automatic torque boost
● Selectable PNP/NPN input signal

● 2nd motor control and parameter setting
● Built-in Dynamic braking transistor as standard
● Enhanced process PID control
● Built-in RS485 (LS Bus / Modbus RTU) communication
● Cooling fan On/Off control & Easy change
● Remote control using external keypad * RJ45 cable(Optional)
● Upgraded functions: Sleep & Wake-up (Energy savings)
KEB (Kinetic Energy Buffering) protection
Low leakage PWM algorism
● Monitoring & commissioning PC based software tool (Drive View)
● Footprint EMC Filter (Option)
● Communication options
- DeviceNet, EtherNet, Profibus-DP, CANOpen

General specification
Model number: SV iG5A-1 004 008 015
Motor rating [HP] 0.5 1 2
[kW] 0.4 0.75 1.5
Output rating Capacity [kVA] 0.95 1.9 3.0
Current [A] 2.5 5 8
Voltage [V] Three-phase 200 ~ 230V
Frequency [Hz] 0.1 ~ 400Hz
Input rating Voltage [V] Single-phase 200 ~ 230V (+10%, -15%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight [kg] 0.77 1.12 1.84
Model number: SV iG5A-2 004 008 015 022 037 040 055 075 110 150 185 220
Motor rating [HP] 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
[kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Output rating Capacity [kVA] 0.95 1.9 3 4.5 6.1 6.5 9.1 12.2 17.5 22.9 28.2 33.5
Current [A] 2.5 5 8 12 16 17 24 32 46 60 74 88
Voltage [V]

Three-phase 200 ~ 230V

Frequency [Hz]

0.1 ~ 400Hz

Input rating Voltage [V]

Three-phase 200 ~ 230V (+10%, -15%)

Frequency [Hz]

50 ~ 60Hz (±5%)
Weight [kg] 0.76 0.77 1.12 1.84 1.89 1.89 3.66 3.66 9.00 9.00 13.3 13.3
Model number: SV iG5A-4 004 008 015 022 037 040 055 075 110 150 185 220
Motor rating [HP] 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
[kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Output rating Capacity [kVA] 0.95 1.9 3 4.5 6.1 6.5 9.1 12.2 18.3 22.9 29.7 34.3
Current [A] 1.25 2.5 4 6 8 9 12 16 24 30 39 45
Voltage [V]

Three-phase 380 ~ 480V

Frequency [Hz]

0.1 ~ 400Hz

Input rating Voltage [V]

Three-phase 380 ~ 480V (+10%, -15%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight [kg] 0.76 0.77 1.12 1.84 1.89 1.89 3.66 3.66 9.00 9.00 13.3 13.3
Control spec Control method V/f, Slip compensation, Sensorless vector

Speed reference resolution Digital command: 0.01Hz / Analog reference: 0.06Hz (Max freq., 60Hz)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared, User custom V/f
Overload capacity 150% for 1 minute
Torque boost Auto & manual torque boost
Operation Keypad display 4 digit, 7 segment LED
Operation method Keypad / Terminal / Communication
Frequency setting Analog: 0 to 10V / -10 to 10V / 0 to 20mA / Digital: Keypad
Operation function PID control / Up-Down operation / 3-Wire operation
Input signal Multi-function terminal PNP / NPN selectable
(P1 ~ P8) 8 points (programmable)
Output signal Multi-function relay Fault output & drive status output (N.O., N.C.) Less than AC250V, 0.3A / Less than DC 30V 1A

Multi-function open collector DC24V (less than 50mA)
Analog output 0 to 10Vdc (less than 10mA): frequency / current / voltage / DC voltage selectable
Protection Drive trip Over voltage / Low voltage / Over current / Over Current 2 / Ground fault / Drive overheat / Output phase open /
Drive overload / Overload trip / Communication error / Frequency command loss / Hardware fault / Fan fault / Brake error / etc.
Drive alarm Stall prevention, Overload
Enclosure IP20, NEMA1 (Optional)
Option Cable, conduit kit Remote cable(2M/3M/5M) plus external keypad, Conduit kit for NEMA 1
Communication DeviceNet, EtherNet, CANOpen, Profibus-DP
Others Built-in Dynamic braking transistor, Built-in RS485(LS Bus / Modbus RTU)

Model Number

SV 015 iG5A - 2
Motor rating
004: 0.4kW ~ 220: 22kW

Symbol Input rating
1 Single-phase, 200 ~ 230V
2 Three-phase, 200 ~ 230V
4 Three-phase, 380 ~ 480V

LS drive brand Series name
iG5A

Symbol Type
FB Field bus communication
EN EMC Filter
ENC

EMC Filter + Field bus communication

FB

10

Variable Frequency Drive

iS7 High Torque Performance and Precise VFD

3 phase 200V : 0.75~75kW(1~100HP), 200~230V
3 phase 400V : 0.75~375kW(1~500HP), 380~480V

● Constant torque / Variable torque dual rating
● Selectable V/f, V/f PG, sensorless vector, sensored vector
● 150 MIPS(million instructions per second) high speed DSP
● High performances & functions:
Droop control (automatic torque balance)
KEB (Kinetic Energy Buffering) protection
Ride Through (LV Trip Delay) protection
Under Load Trip protection
Power brake & Flux Brake function
Static motor parameter Auto-tuning*
● Easy to control: Easy Start Mode, User & Macro group,
Multi Function Key
● 2nd motor sensorless control and parameter setting

● Available IP54 enclosure(0.75˜22kW[1˜30HP]) as built-in option
● Built-in RS485(LS Bus / Modbus RTU) communication
● Built-in Dynamic braking transistor (0.75˜22kW[1˜30HP])
● Available EMC Filter & DC Reactor as built-in option
EMC Filter(0.75˜22kW[1˜30HP]) / DC Reactor(0.75˜160kW[1˜215HP])
● Wide graphic LCD keypad (6 different languages)
● PLC board (optional):
Master-K platform: 14 max. inputs & 7 max. outputs
● Extension I/O boards (Optional):
11 max. inputs & 6 max outputs
● Communication boards (Optional):
Profibus-DP, DeviceNet, Modbus TCP, Rnet, LonWorks, CANopen
● Monitoring & commissioning PC based software tool (Drive View)

General specification
Model number: SV iS7-2 0008 0015 0022 0037 0055 0075 0110 0150 0185 0220

Motor rating [HP] 1 2 3 5 7.5 10 15 20 25 30
[kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
Output rating Capacity [kVA] 1.9 3 4.5 6.1 9.1 12.2 17.5 22.9 28.5 33.5
Current (CT) [A] 5 8 12 16 24 32 46 60 74 88
Current (VT) [A] 8 12 16 24 32 46 60 74 88 124
Voltage [V]

Three-phase 200 ~ 230V
Frequency [Hz] 0.01 ~ 400Hz (Sensorless-1 control: 0.01~300Hz, Sensorless-2 or Sensored control: 0.01~120Hz)
Input rating Voltage [V]

Three-phase 200 ~ 230V (-15% ~ +10%)

Frequency [Hz]

50 ~ 60Hz (±5%)
Current (CT) [A] 4.3 6.9 11.2 14.9 22.1 28.6 44.3 55.9 70.8 85.3
Current (VT) [A] 6.8 10.6 14.9 21.3 28.6 41.2 54.7 69.7 82.9 116.1

0300 0370 0450 0550 0750
40 50 60 75 100
30 37 45 55 75
46 57 69 84 116
116 146 180 220 288
146 180 220 288 345

121 154 191 233 305
152 190 231 302 326

Model Number
SV 0008 - 2 N O F D W
LS drive brand Motor rating
0008 : 0.75kW ~ 3750 : 375kW

Series name
iS7

Symbol Input rating
2 Three-phase, 200 ~ 230V
4 Three-phase, 380 ~ 480V

Symbol Loader
N Non

Loader
S Graphic

Loader

Symbol UL Certification
O Open type
E Enclosed Type 1

(NEMA1)
P NEMA 12

Symbol Filter
None Not available
F EMC filter

Symbol DCR
None Not available
D DC Reactor

Symbol Application
None Normal application
W Web application

Model number: SV iS7-4 00080015002200370055007501100150 01850220 03000370 0450 0550 0750
Motor rating [HP] 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100
[kW] 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
Output rating Capacity [kVA] 1.9 3 4.5 6.1 9.1 12.2 17.5 22.9 29.7 34.3 46 57 69 84 116
Current (CT) [A] 2.5 4 6 8 12 16 24 30 39 45 61 75 91 110 152
Current (VT) [A] 4 6 8 12 16 24 30 39 45 61 75 91 110 152 183
Voltage [V]

Three-phase 380 ~ 480V

Frequency [Hz]

0.01 ~ 400Hz (Sensorless-1 control: 0.01~300Hz, Sensorless-2 or Sensored control: 0.01~120Hz)

Input rating Voltage [V]

Three-phase 380 ~ 480V (-15% ~ +10%)

Frequency [Hz]

50 ~ 60Hz (±5%)
Current (CT) [A] 2.2 3.6 5.5 7.5 11.0 14.4 22.0 26.6 35.6 41.6 55.5 67.9 82.4 102.6 143.4
Current (VT) [A] 3.7 5.7 7.7 11.1 14.7 21.9 26.4 35.5 55.7 67.5 81.7 101.8 123 143.6 173.4
Control spec Control method V/f, V/f PG, Slip compensation, Sensorless-1 vector, Sensorless-2 vector, Sensored vector
Speed reference resolution Digital command: 0.01Hz / Analog reference: 0.06Hz (Max freq., 60Hz)
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared, User custom V/f
Overload capacity CT(Heavy duty): 150% for 1 minute, VT(Normal duty): 110% for 1 minute
Torque boost Auto & Manual torque boost
Operation Keypad display Wide graphic LCD keypad (available 6 languages)
Operation method Keypad / Terminal / Communication
Frequency setting Analog: 0 to 10V / -10 to 10V/ 0 to 20mA / Digital: Keypad
Operation function PID control / Up-Down operation / 3-Wire operation / DC braking / Frequency limit / Second function / Slip compensation / Reverse rotation prevention /
Auto restart / Drive By-pass / Auto-tuning / Flying star / Energy buffering / Power braking / Flux braking / Low leakage / MMC / Easy start
Input signal Multi-function terminal PNP / NPN selectable
(P1 ~ P8) 8 points (programmable)
Output signal Multi-function relay Fault output & drive status output (N.O., N.C.) Less than AC250V, 1A / Less than DC 30V 1A

Multi-function open collector DC24V (less than 50mA)
Analog output 0 to 10Vdc (less than 10mA): frequency / current / voltage / DC voltage selectable
Protection Drive trip Over current / Over voltage / Low current / External trip / Ground fault / Drive overheat / I/O phase open / Overload / Communication error /
Frequency command loss / Hardware fault / Fan fault / Pre-PID fault / No motor trip / External brake trip / etc.
Drive alarm Stall prevention / Overload / Light load / Encoder connection error / Keypad command loss /
Speed command loss
Enclosure IP00 (30~75kW, 200V/ 90~375kW, 400V), IP21 (0.75~22kW, 200V / 0.75~75kW, 400V), IP54 / NEMA12 (0.75~22kW, 200V/ 400; Optional)
Option Board, Cable, Keypad Graphic LCD keypad(IP21), Extension I/O, Isolation I/O, Encoder board, PLC board, Remote cable(2M/3M)
Communication Profibus-DP, DeviceNet, Modbus TCP, Rnet, LonWorks, CANopen, EtherNet/IP
Others Built-in Dynamic braking transistor (0.75~22kW[1~30HP]), Built-in RS485(LS Bus / Modbus RTU)

09 0011 00 1320 1600 1850 2200 2800 3150 3750
120 150 180 225 250 300 375 420 500
90 110 132 160 185 220 280 315 375
139 170 201 248 286 329 416 467 557
183 223 264 325 370 432 547 613 731
223 264 325 370 432 547 613 731 877

174.7 213.5 255.6 316.3 404 466 605 674 798
212.9 254.2 315.3 359.3 463 590 673 796 948

iS7

※ ABS Standard - Acquired (up to 90kW) / In Progress (above 90kW)
※ DNV Standard - Acquired

ISO14001, ISO9001

LS Inverter Series 11

Variable Frequency Drive

iP5A 3 phase 2Fan & Pump specialized VFD

00V : 5.5~30kW(1~400HP), 200~230V
3 phase 400V : 5.5~450kW(1~600HP), 380~480V

● Specialized functions for Fan & Pump:
Advanced PID control (Pre-PID, Dual PID)
Multi Motor Control function
(Up to 4 motors: 5.5 ˜ 90kW[7.5˜125HP])
● Energy saving & High efficiency:
Sleep & Wake-up function
Flying Starting function
Automatic energy saving function
Flux Braking Algorithm
● Improved protection functions:
Pre-heater function
Low Leakage PWM
Safety stop function
Automatic carrier frequency change

● Selectable V/f, Sensorless vector control
● Long-life condenser & Simple framework
● Easy Start function
● Selectable PNP/NPN input signal
● Plug-in type control terminals
● Cooling fan On/Off control
● Built-in RS485(LS Bus) communication
● Communication boards (Optional):
Modbus RTU, DeviceNet, Profibus-DP, LonWorks,
BACnet, Modbus TCP*, CANOpen, CC-Link
● Monitoring & commissioning PC based software tool
(Drive View)
● DNV Certification

Control spec Control method V/f, Slip compensation, Sensorless vector
Speed reference resolution Digital command: 0.01Hz (below 100Hz), 0.1Hz(over 100Hz) / Analog reference: 0.1Hz/60Hz
Frequency accuracy Digital command: 0.01% of Max output freq. / Analog signal command of 0.1% of Max output freq.
V/f curve Linear, Squared, User custom V/f
Overload capacity 110% for 1 minute, 120% for 1 minute(based on ambient 25°C)
Torque boost Auto & Manual(0 ~ 15%) torque boost
Operation Keypad display 32 characters LCD keypad
Operation method Keypad / Terminal / Communication
Frequency setting Analog: 0 ~ 12V / -12V ~ 12V / 4 ~ 20mA or 0 ~ 20mA / Pulse / Ext - PID / Digital: Keypad
Operation function DC braking / Frequency limit / Frequency jump / Second function / Slip compensation / Reverse rotation prevention / Auto restart / Drive By-pass / Auto-tuning
/ PID control / Flying star / Safety stop / Flux braking / Low leakage / Pre-PID / Dual-PID / MMC / Easy start / Pre-heater
Input signal Sart signal Forward / Reverse
Multi-step Up to 8 speeds can be set including JOG (Use Programmable Digital Input terminal)
Multi-step Accel/Decel time 0.1~6,000 sec, Up to 4 types can be set (Use Multi-function terminal)
Accel/Decel curve : Linear, U curve, S curve
Emergency stop Interrupts the Output from Drive
JOG JOG operation
Fault reset Trip status is removed when Protection function is active
Output signal Operating status Frequency detection level / Overload alarm / Stalling / Over voltage / Low voltage / Drive overheating / Run / Stop / Constant speed /
Drive By-pass / Speed search
Fault output Contact output (3A, 3C, 3B) - AC250V 1A, DC30V 1A
Indicator Ouput frequency / Output current / Output voltage / DC Link voltage(Output valtage:0~10V)
Protection Drive trip Over voltage / Low voltage / Over current 1, 2 / Ground fault / Drive overheating / Electronic thermal / Output phase open / overload /
External Fault A, B / Communication Error / Frequency command loss / Hardware fault / Option fault / etc
Drive alarm Stall prevention / Overload / Temperature sensor fault
Enclosure IP20/UL type 1(5.5~11kW[7.5~15HP]), IP00/UL open type(15~450kW[20~600HP])
Option Board, cable, keypad LCD Keypad, Remote cable(2M/3M/5M), Sub-E board(Current output)
Communication DeviceNet, Profibus-DP, Modbus TCP, Modbus RTU, Matasys N2, LonWorks, BACnet, CC-Link, CANopen

0055 iP5A - 2 N O L
LS drive brand Motor rating
0008 : 0.75kW ~ 4500 : 450kW

Series name
iP5A

Symbol Input rating
2 Three-phase, 200 ~ 230V
4 Three-phase, 380 ~ 480V

Symbol Loader
None Loader
N Non Loader

Symbol UL Certification
O Open type
E Enclosed Type 1

Symbol DCR
None Not available
L DC Reactor

Symbol Certificate
(CLASS) DNV

General specification

(CLASS)

Model number: SV iP5A-2 0055 0075 0110 01500185 0220 0300
Motor rating [HP] 7.5 10 15 20 25 30 40
(Fan/Pump) [kW] 5.5 7.5 11 15 18.5 22 30
Current [A] 24 32 46 60 74 88 115
(110% overload) Normal duty: 110% for 1 minute
Motor rating [HP] 5 7.5 15 15 20 25 30
(General load) [kW] 3.7 5.5 7.5 11 15 18.5 22
Current [A] 17 23 33 44 54 68 84
(150% overload) Heavy duty: 150% for 1 minute
Output rating [kVA] 9.1 12.2 17.5 22.9 28.2 33.5 43.8
Voltage [V]

Three-phase 200 ~ 230V
Frequency [Hz] 0.01 ~ 120Hz
Input rating Voltage [V]

Three-phase 200 ~ 230V (-15% ~ +10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight Non DCR type [kg] 4.9 6 6 13 13.5 20 20
Model number: SV iP5A-4 0055 0075 0110 0150 0185 0220 0300 0370 0450 0550 0750 0900 1100 1320 1600 2200 2800 3150 3750 4500

Motor rating [HP] 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 215 300 350 400 500 600
(Fan/Pump) [kW] 5.5 7.5 11 151 8.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375 450
Current [A] 12 16 24 30 39 45 61 75 91 110 152 183 223 264 325 432 547 613 731 877
(110% overload) Normal duty: 110% for 1 minute
Motor rating [HP] 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 215 300 350 400 500
(General load) [kW] 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 280 315 375
Current (Non DCR / DCR) [A] 8.8 12 16 22/24 28/30 34/39 44/45 61 75 91 110 152 183 223 264 325 432 547 613 731
(150% overload) Heavy duty: 150% for 1 minute
Output rating [kVA] 9.6 12.7 19.1 23.9 31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8 178 210 259 344 436 488 582 699
Voltage [V] Three-phase 380 ~ 480V
Frequency [Hz] 0.01 ~ 120Hz
Input rating Voltage [V] Three-phase 380 ~ 480V (-15% ~ +10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight Non DCR type [kg] 4.9 6 6 12.5 13 20 20 27 27 29 42 43 243 280 380
Built-in DCR type [kg] 19.5 19.5 26.5 26.5 39 40 42 67 68 101 101 114 200 200

Model Number
SV

12

Variable Frequency Drive

iV5 High duty full flux vector control VFD

3 phase 200V : 2.2~37kW(3~50HP), 200~230V
3 phase 400V : 2.2~800kW(3~1067HP), 380~480V
400V DC input type : 5.5~500kW(7.5~666HP)

● Ultimate performance solution for System Drive
● Advanced Speed & Torque control
(200% instantaneous torque: Max. 250%)
● Precious Speed & Position synchronization operation
● Static motor parameter Auto-tuning
● Draw / Droop / Process PID control
● Highly precious control through optional Sincos Encoder
● Synchronous motor sensorless control
(SPM & IPM motors)
● Specialized functions for various applications
Load balance function
Diameter calculation / Taper function
Splicing / Inertia compensation function
Quick stop function

● Built-in Dynamic braking transistor (2.2~22kW[3~30HP])
● User-friendly LCD keypad (Detachable)
● Plug-in type control terminals
● Extension I/O boards (Optional):
EL I/O (for Elevator application)
Encoder division (open collector)
Synchronization option (Speed/Position control)
Sincos encorder
● Communication boards (Optional)
RS485(LS Bus / Modbus RTU)
Profibus-DP
DeviceNet
● Monitoring & commissioning PC based software tool
(Drive View)

General specification
Model number: SV iV5-2 022 037 055 075 110 150 185 220 300 370
Motor rating [HP] 3 5 7.5 10 15 20 25 30 40 50
[kW] 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37
Output rating Capacity [kVA] 4.5 6.1 9.1 12.2 17.5 22.5 28.2 33.1 46 55
Current [A] 12 16 24 32 46 59 74 88 122 146
Voltage [V] Three-phase 200 ~ 230V
RPM 0 ~ 3600 [RPM]
Input rating Voltage [V]

Three-phase 200 ~ 230V (+10%, -10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight Mold cover type [kg] 6 6 7.7 7.7 13.7 13.7 20.3 20.3
Metallic cover type [kg] 14 14 28 28 28 28 42 42

Model Number
SV 022 iV5 - 2 DB (MD) (DC)
LS drive brand Motor rating
022: 2.2kW ~ 80000: 800kW

Series name
iV5

Symbol Input rating
2 Three-phase, 200 ~ 230V
4 Three-phase, 380 ~ 480V

Symbol

Dynamic Brake
None Not available
DB

Dynamic Braking

Symbol Cover type
None Metallic cover
(MD) Mold cover*

, 380V
Symbol Rated voltage
None 200~230V or 380~480V
**** 380V, 460V, 480V

Symbol Input type
None AC Input
(DC) DC Input

1320 1600 2200 2800 3150 3750 5000 8000

175 215 300 373 420 500 666 1067
132 160 220 280 315 375 500 800
200 250 329 416 468 557 732 1105
264 325 432 546 614 731 960 1384

112 112 175 243 380 380

476 1300

Model number: SV iV5-4 022 037 055 075 110 150 185 220 300 370 450 550 750 900 1100
Motor rating [HP] 3 5 7.5 10 15 20 25 30 40 50 60 75 100 120 150
[kW] 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110
Output rating Capacity [kVA] 4.5 6.1 9.1 12.2 18.3 22.9 29.7 34.3 46 57 70 85 116 140 170
Current [A] 6 8 12 16 24 30 39 45 61 75 91 110 152 183 223
Voltage [V] Three-phase 380 ~ 480V
RPM 0 ~ 3600 [RPM]
Input rating Voltage [V] Three-phase 380 ~ 480V (+10%, -10%)
Frequency [Hz] 50 ~ 60Hz (±5%)
Weight Mold cover type [kg] 6 6 7.7 7.7 13.7 13.7 20.3 20.3
Metallic cover type [kg] 14 14 28 28 28 28 42 42 63 63 68 98 98
Model number: SV iV5-4 (DC) 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600
Motor rating [HP] 7.5 10 15 20 25 30 40 50 60 75 100 120 150 175 215
[kW] 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160
Output rating Capacity [kVA] 9.1 12.2 18.3 22.9 29.7 34.3 46 57 70 85 116 140 170 200 250
Current [A] 12 16 24 30 39 45 61 75 91 110 152 183 223 264 325
Voltage [V]

380 ~ 480V
RPM 0 ~ 3600 [RPM]
Input rating Voltage [V] DC 540 ~ 680V (+10%,)
Weight [kg] 12 12 24 24.5 25 25 38.5 38.5 50 50 55 79 79 98.5 98.5

2200 2800 3150 3750 5000

300 373 420 500 666
220 280 315 375 500
329 416 468 557 732
432 546 614 731 960

154.5 206 343 343 466

Control spec Control method Sensored Vector (speed sensor)
Speed reference resolution Digital command: 0.1rpm / Analog reference: 。セ0.0005% of Max output freq.
Speed accurancy Digital command: 。セ0.01(0~40°C) of Max output freq. / Analog signal reference: 。セ0.02(25。セ10°C) of Max output freq.
Cut-off frequency of ASR 50Hz
Torque control accuracy 3%
Accel/Decel time 0.00~6000.0 sec
Accel/Decel combination 4 combinations of Accel/Decel time
Aceel/Decel curve Linear / S curve
Frequency setting Analog: -10 to 10V / 4 to 20mA / Digital: Keypad
Input signal Analog input 3 channels (AI1, AI2, AI3): Extention I/O 2 channels (AI4, AI5)
-10 to 10V / 0 to 10V / 10 to 0V / 4 to 20mA / 20 to 4mA / (AI3, AI5[Extention I/O]: Motor NTC/PTC selectable)
Selectable among 15 diferent Multi-function analog inputs
AI3, AI5: NTC is avaliable only with LG-OTIS motors (both of NTC and PTC are available in case of SV2800iV5~SV3750iV5)
Contact input FX, RX, BX, RST, P1~P7
Selectable among 40 diferent Multi-function analog inputs
Output signal Aanalog output 2 channels (AO1, AO2)
-10 to 10V / 10 to -10V / 0 to 10V / 10 to 0V
Selectable among 40 diferent Multi-function analog outputs
Contact output Multi-function contact output: 2 channels (1A-1B, 2A-2B)
Fault contact output: 1 channel (30A-30C, 30B-30C)
Open collector 1 channel (OC1/EG)

Protection Over voltage / Over current / Low voltage / Drive overheat / Drive thermal malfunction / Motor overheat / Motor thermal malfunction /
Overspeed / BX(Instantaneous IGBT gate block) / Fuse open / External fault / Encoder error / Electronic thermal / Overload / IGBT short /
Communication error / etc.

Enclosure IP00 (2.2~22kW[3~30HP]: Mold cover* / 30~374kW[40~500HP]: Metallic cover), IP20 (2.2~22kW[3~30HP]: Metallic cover)
Option Board EL I/O(for Elevator application), Encorder division(open collector), Synchronization option(Speed/Position control), Sincos encorder
Communication RS485(LS Bus / Modbus RTU), Profibus-DP, DeviceNet

LS Inverter Series 13

200~230V

Standard
Standard

Standard
0.1~0.4kW
0.13~0.5HP

Fixed type
7 segment
0.1~0.4kW
0.13~0.5HP

Standard
Standard

Single-phase
0.1~0.4kW
0.13~0.5HP

Three-phase
0.1~0.4kW
0.13~0.5HP

Standard
Standard
Standard
Standard
Standard

Option

NEMA4X Line-up

Option
Option

Standard
Standard
Option
Option

Option
Option

Standard / Multiple
Option

Standard
Standard
Standard
Standard
0.4~22kW
0.5~30HP
Option
0.4~22kW
0.5~30HP

Fixed type
7 segment
0.4~22kW
0.5~30HP

Option
Option
Option
Standard
0.4~22kW
0.5~30HP

Standard
Standard

Single-phase
200~240V
0.1~2.2kW
0.1~3.0HP
Standard
Standard

Standard
0.1~2.2kW
0.1~3.0HP

Fixed type
7 segment
0.1~2.2kW
0.1~3.0HP

Option
Option
Option
Standard
1.5~2.2kW
2.0~3HP
Built-in Standard
0.1~2.2kW
0.1~3.0HP

Standard
Standarad

Standard / Advanced

Single-phase
200~230V 380~480V

0.4~2.2kW
0.5~3HP

0.4~15kW
0.5~20HP

0.4~75kW
0.5~100HP

0.4~2.2kW
0.5~3HP

0.4~2.2kW
0.5~3HP

0.4~2.2kW
0.5~3HP

200~240V
0.4~2.2kW
0.5~3HP

0.4~2.2kW
0.5~3HP

Fixed type
7 segment

iS7 Graphic LCD

Single-phase Three-phase

0.4~15kW
0.5~20HP

0.4~15kW
0.5~20HP

0.4~15kW
0.5~20HP

200~240V
0.4~15kW
0.5~20HP

0.4~15kW
0.5~20HP

0.4~15kW
0.5~20HP

380~480V
0.4~75kW
0.5~100HP

0.4~15kW
0.5~20HP

0.4~15kW
0.5~20HP

Option
30~75kW
40~100HP
Built-in Option
30~45kW
40~60HP
Built-in
30~75kW
40~100HP

Standard
0.4~22kW
0.5~30HP

Detachable type
iS7 Graphic LCD

0.4~75kW
0.5~100HP

0.4~22kW
0.5~30HP

0.4~1.5kW
0.5~2HP

0.4~22kW
0.5~30HP

0.4~22kW
0.5~30HP

Three-phase

Standard
Standard
Standard
Standard
Standard
0.4~7.5kW
0.5~10HP
Option
0.4~7.5kW
0.5~10HP

Fixed type
7 segment
0.4~7.5kW
0.5~10HP

Option
Option
Option
Standard
0.4~7.5kW
0.5~10HP

Standard
Standard
Option
Option

Option
Option

0.4~7.5kW
0.5~10HP

Three-phase
200~240V 380~480V
0.4~7.5kW
0.5~10HP

Builnt-in Option
0.4~7.5kW
0.5~10HP

Built-in
0.4~2.2kW
0.5~3HP

Built-in
0.4~22kW
0.5~30HP

Variable Frequency Drive

Comparison
Model Series iE5 M100 iG5A G100 S100
Input Phase
Voltage Range
Motor rating

Heavy Duty (Constant Torque)
Normal Duty (Variable Torque)
Control method V/f
Sensorless Vector
Sensored Vector
Enclosure IP20

IP211)

IP54

IP66

Keypad Type
Built-in

Option

Remote cable 2 meters
3 meters
5 meters
Braking transistor

EMC Filter

DC Reactor

RS485(LS Bus)
Modbus RTU
Modbus TCP
DeviceNet
Profibus-DP
Fnet(LS PLC link)
Rnet
LonWorks
CANopen
BACnet
EtherNet/IP
CC-Link
Metasys N2
Encoder
Sin/Cos encoder
PLC
I/O type
Extension I/O
Elevator I/O
Synchronization I/O
1) UL Enclosed Type 1 with conduit box installed.

14

Variable Frequency Drive

Comparison

1) UL Enclosed Type 1 with conduit box installed.
2) Enclosed IP54 Type, UL Enclosed Type 12

Model Series iP5A H100 iS7 iV5
Input Phase Three-phase Three-phase Three-phase Three-phase
Voltage Range 200~230V 380~480V 200~240V 380~480V 200~230V 380~480V 200~230V 380~480V
Motor rating 5.5~30kW 5.5~450kW 0.75~18.5kW 0.75~500kW 0.75~22kW 0.75~375kW 2.2~37kW 2.2~800kW
7.5~40HP 7.5~600HP 0.1~22HP 0.1~800HP 1~30HP 1~500HP 3~50HP 3~1067HP
Heavy Duty (Constant Torque) Standard Standard Standard
Normal Duty (Variable Torque) Standard Standard Standard
Control method V/f Standard Standard Standard
Sensorless Vector Standard Standard
Sensored Vector Option Standard
Enclosure IP00 Standard Standard Standard Standard Standard Standard 30~75kW
15~30kW 15~45kW 0.75~220kW 30~75kW 90~375kW 2.2~37kW 2.2~375kW
20~40HP 20~600HP 1.0~350HP 40~100HP 125~500HP 3~30HP 3~500HP
IP20 Standard Standard Standard Standard Standard
5.5~11kW 0.75~18.5kW 0.75~220kW 0.75~22kW 0.75~75kW 5.5~22kW
7.5~15HP 0.1~22HP 1.0~350HP 1~30HP 1~100HP 7.5~30HP
IP211) Option Option Option Option Option
5.5~11kW 5.5~11kW 0.75~18.5kW 0.75~90kW 0.75~22kW 0.75~75kW
7.5~15HP 7.5~15HP 0.1~22HP 0.1~120HP 1~30HP 1~100HP
IP54 Option 2)
0.75~22kW
1~30HP
Keypad Type Detachable type Detachable type Detachable type Detachable type
Built-in 37~450kW 0.75~90kW 90~160kW 2.2~800kW
50~600HP 0.1~22HP 125~215HP 3~1067HP
Option 0.75~75kW
1~100HP
Remote cable 2 meters Option Option Option
3 meters Option Option Option
5 meters Option
Braking transistor Standard Standard
0.75~22kW 2.2~22kW
1~30HP 3~30HP
EMC Filter Built-in Built-in Option
0.75~500kW 0.75~22kW
0.1~800HP 1~30HP
DC Reactor Built-in Option Built-in Built-in Option
15~280kW 37~500kW 0.75~22kW 0.75~220kW
20~350HP 50~800HP 1~30HP 1~300HP
RS485(LS Bus) Standard / Option Standard Standard Option
Modbus RTU Option Standard Standard Option
Modbus TCP Option Option
DeviceNet Option Option Option
Profibus-DP Option Option Option
Fnet(LS PLC link)
Rnet Option
LonWorks Option Option Option
CANopen Option
BACnet Option Standard
EtherNet/IP Option
CC-Link Option Option Option
Metasys N2 Option Standard
Encoder Option Standard
Sin/Cos encoder Option
PLC Option
Extension I/O Option Option Option
Elevator I/O Option
Synchronization I/O Option Option

LS Inverter Series 15

Variable Frequency Drive

Option list

Series Option Name Series Option Name
M100

iG5A

iE5

G100

S100

iS7

H100

iV5

Common

M100 remote keypad
Remote cable (1m, 2m, 3m, 5m)
Modbus RTU
iG5A remoted keypad
Remoted cable (2m, 3m, 5m)
2 Port Ethernet/IP (Modbus TCP)
Profibus-DP
CANopen
G100 remote keypad *
Remote cable (1m, 2m, 3m, 5m)
Modbus TCP
PROFInet
EtherCAT
EtherNet/IP
Profibus-DP
CANopen
Scalable I/O
S100 LCD keypad
S100 remote keypad (LED)
Remote cable (1m, 2m, 3m, 5m)
Lonworks
H100 remote keypad
Remote cable (1m, 2m, 3m, 5m)
EtherNet/IP
RAPIEnet
PROFInet
Modbus TCP
DeviceNet
CANopen
Profibus-DP
CC-Link
Lonworks
R-Net / F-Net
Encoder
24V Encoder
Position control
Synchronization control
Scalable I / O
PLC
Safety
Binary Input
iS7 LCD keypad
Remote cable (2m, 3m)

RS-485
Modbus RTU
DeviceNet
Profibus-DP
CC-Link
Synchronization
EL I / O
SIN / COS + Endat
Scalable I / O
24V Encoder
Parameter Copy Unit
Smart Copier

The table below describes a list of options for various LSIS drives.
Please contact LSIS for further details on our drive options.

* G100/M100 remote keypads are compatible.

2019. 10 ⓒ 2003.04 LSIS Co.,Ltd. All rights reserved. / (70) 2019. 10 Human Power

•For your safety, please read user's manual thoroughly before operating.
•Contact the nearest authorized service facility for examination, repair, or adjustment.
•

Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
•Any maintenance and inspection shall be performed by the personnel having expertise concerned.

•According to The WEEE Directive, please do not discard the device with your household waste.

Safety Instructions

• LSIS Beijing Office (China)
Tel: 86-10-5761-3127 Fax: 86-10-5761-3128 E-Mail: sson@lsis.com
• LSIS Guangzhou Office (China)
Tel: 86-20-8326-6784 Fax: 86-20-8326-6287 E-Mail: sojhtroh@lsis.com
• LSIS Qingdao Office (China)
Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 E-Mail: sson@lsis.com
• LSIS Chengdu Office (China)
Tel: 86-28-8670-3200 Fax: 86-28-8670-3203 E-Mail: yangcf@lsis.com
• LSIS ShenYang Office (China)
Tel:86-24-2321-9050 Fax: 86-24-8386-7210 E-Mail: yangcf@lsis.com
• LSIS Jinan Office (China)
Tel: 86-531-8699-7826 Fax: 86-531-8697-7628 E-Mail: yangcf@lsis.com
• LSIS Co., Ltd. Tokyo Office (Japan)
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: jschuna@lsis.com
• LSIS Co., Ltd. Rep. Office (Vietnam)
Tel: 84-28-3823-7890 E-Mail: sjbaik@lsis.com
• LSIS Moscow Office (Russia)
Tel: 7-499-682-6130 E-Mail: jdpark1@lsis.com
• LSIS Jakarta Office (Indonesia)
Tel: 62-21-2933-7614 E-Mail: dioh@lsis.com
• LSIS Bangkok Office (Thailand)
Tel: 66-90-950-9683 E-Mail: sjleet@lsis.com

Head Quarter
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea
Tel : 82-2-2034-4286 Fax : 82-2-2034-4648 E-mail : drivesales@lsis.com
Overseas Subsidiaries
• LSIS(Shanghai) Co., Ltd. /CHINA
Tel : 86-21-5237-9977(609) Fax : 86-21-5237-7189
• LSIS(Dalian) Co., Ltd. (Dalian, China)
Tel: 86-411-8730-7510 Fax: 86-411-8730-7560 E-Mail: jiheo@lsis.com
• LSIS(Wuxi) Co., Ltd. (Wuxi, China)
Tel: 86-510-8534-6666-8005 Fax: 86-510-8534-4078 E-Mail: sunhwank@lsis.com
• LS VINA Industrial Systems Co., Ltd. (Hanoi, Vietnam)
Tel: 84-24-3882-0222 Fax: 84-24-3882-0220 E-Mail: jhchoi4@lsis.com
• LSIS Middle East FZE (Dubai, U.A.E.)
Tel: 971-4-886-5360 Fax: 971-4-886-5361 E-Mail: hschoib@lsis.com
• LSIS Europe B.V. (Hoofddorf, Netherlands)
Tel: 31-20-654-1420 Fax: 31-20-654-1429 E-Mail: htha@lsis.com
• LSIS Japan Co., Ltd. (Tokyo, Japan)
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: jschuna@lsis.com
• LSIS USA Inc. (Chicago, U.S.A.)
Tel: 1-800-891-2941 Fax: 1-847-383-6543 E-Mail: sales.us@lsis.com
Overseas Branches
• LSIS Shanghai Office (China)
Tel: 86-21-5237-9977(609) Fax: 86-21-5237-7189 E-Mail: ygeo@lsis.com